19. DEHUMIDIFICATION

This function is always active when the humidity probe is enabled. By setting parameter P32 = zero, the humidity probe

will be enabled. Dehumidification occurs by using the solenoid valve and the compressor switching on or by setting
parameter P71 = 2, when output K3 can be used to control a humidity extraction fan or a dehumidifier..

19.1. Dehumidification with compressor

This type of dehumidification is possible when parameter P71 is different from 2.
The graphs below display the management modes.

Case 1

Setpoint+zm+ist

Setpoint

Sonda Umidità

Setpoint+zm

Setpoint

P44

P29

tempo

Elettrovalvola

Compressore

On

Off

Off

On

The solenoid valve is switched on for a period of time determined by parameter P44. If within this time the humidity

probe drops below the setpoint + dead zone value, the solenoid valve will switch off and the compressor will switch on for
the ‘on’ enforced time determined by parameter P29.

If the probe drops below the setpoint + dead zone value before time P44 is over, the solenoid valve will switch off and

the compressor will switch on for the period of time determined by parameter P29.


If parameter P71 is set at 1 (output K3 does not manage the solenoid valve, only the light in the cell), dehumidification

will only require the compressor, which will be activated P44 seconds after the dehumidification request.