15.5

Errors handling

Ignition phase:

If no flame is detected during ignition phase, the burner will maintain the ignition speed.

Heating phase:

If no flame is detected during heating phase, the activation relay is turned off, the fan returns to the ignition speed for 10 seconds and

after 20 seconds the ignition attempt is repeated.

Room/boiler burner fault alarm:

If the ignition control board activates the room/boiler burner fault digital input, a recovery procedure is performed. The procedure

consists in 3 ignition attempts before signalling the alarm.

Room burner alarm

The room burner fan speed is constantly checked through the Hall input. If the speed set for the room fan burner differs more than

parameter b5 from the Hall sensor feedback for a time longer than parameter b6, the alarm is signalled.

Boiler burner alarm:

The boiler burner fan speed is constantly checked through the Hall input. If the speed set for the boiler fan burner differs more than

parameter b12 from the Hall sensor feedback for a time longer than parameter b13, the alarm is signalled.