WORKING SETPOINT SETTING
The working setpoint is programmable within the lim-
its established with the parameters r1 and r2.
To modify the working setpoint value:

a) keep pushed the key

the instrument displays the actual value

the compressor LED flashes quickly

b) push and release the key

or

as long

as the instrument displays the desired value

the working setpoint value gets increased or decreased

c) after the modify release the key

last

the instrument automatically turns out from the working

setpoint setting procedure.

CONFIGURATION PARAMETERS SETTING
Configuration parameters are arranged on two levels.
To gain access to the first level:

a) keep pushed for four seconds at least the keys

and

passed four seconds the instrument displays the label

PA

To select a parameter:

a) push and release the key

or

as long

as the instrument displays the label of the de-
sired parameter

To modify a parameter value:

a) keep pushed the key

the instrument displays the actual value

b) push and release the key

or

as long

as the instrument displays the desired value

the parameter value gets increased or decreased

c) after the modify release the key

last

the instrument displays the label of the parameter again

To gain access to the second level:

a) enter inside the first level and select the label

PA

b) keep pushed the key

the instrument displays the actual value

c) push and release the key

or

as long

as the instrument displays -19

the label value gets increased or decreased

d) after the modify release the key

last

the instrument displays the label PA again

e) keep pushed for four seconds at least the keys

and

passed four seconds the instrument displays the first pa-

rameter of the second level

To turn out from the configuration parameters
setting procedure:

a) keep pushed for four seconds at least the keys

and

or do not operate with the keys

for fifty seconds at least.

ENGLISH

EC 6-294

EC 6-294

EC 6-294

EC 6-294

EC 6-294

Quick reference

1

4

communication

n0

0

2

---

0

instrument functioning in the network (®)

n1

0

8

---

0

instrument address (®)

n3

0

1

---

0

enabling to work as slave instrument (§) (®)

n4

0

240

sec.

0

delay to the resources implementation in the slave instrument (®)

nA

0

15

---

0

resources to implement in the slave instrument (®)

Additional informations:

• the symbol (§) indicates that the parameter is of the first level
• the symbol (*) indicates that the unit of measure depends from the parameter /8
• the symbol (®) indicates that the parameter is available on request only
• the symbol (**) indicates that the unit of measure depends from the parameter db.