WORKING SETPOINT AND CONFIGURATION PARAMETERS

10.1 Working setpoint

LABEL MIN. MAX. U.M.

DEF. WORKING SETPOINT

r1

r2

°C/°F

(5)

0.0

working setpoint

10.2 First level parameters

LABEL MIN. MAX. U.M.

DEF. PASSWORD

PA

-55

99

---

0

password

LABEL MIN. MAX. U.M.

DEF. MEASURE INPUTS

/1A

-10

10.0 °C/°F

(5)

0.0

cabinet probe calibration

/1b

-10

10.0 °C/°F

(5)

0.0

evaporator probe calibration

LABEL MIN. MAX. U.M.

DEF. REGULATOR

r0

0.1

15.0 °C/°F

(5)

2.0

hysteresis (differential, it is relative to the working setpoint)

LABEL MIN. MAX. U.M.

DEF. SERIAL NETWORK (EVCONET)

n3

0

1

---

0

authorization to implement the remote controls coming from the master (it is important if

n0 = 2 and n1 ≠ 0; 1 = YES)

LABEL MIN. MAX. U.M.

DEF. ENERGY SAVING (the working setpoint becomes r8)

Hr1

0.0

23.5 h.damin

(6)

0.0

Energy Saving cycle activation time

Hr2

0.0

23.5 h.damin

(6)

0.0

Energy Saving cycle length

LABEL MIN. MAX. U.M.

DEF. REAL TIME DEFROST

Hd1 0.0

23.5 h.damin

(6)

- - -

first defrost activation time (it is important if dE = 3; - - - = it will never be activated)

(7)

Hd2 0.0

23.5 h.damin

(6)

- - -

second defrost activation time (it is important if dE = 3; - - - = it will never be activated)

(7)

Hd3 0.0

23.5 h.damin

(6)

- - -

third defrost activation time (it is important if dE = 3; - - - = it will never be activated)

(7)

Hd4 0.0

23.5 h.damin

(6)

- - -

fourth defrost activation time (it is important if dE = 3; - - - = it will never be activated)

(7)

Hd5 0.0

23.5 h.damin

(6)

- - -

fifth defrost activation time (it is important if dE = 3; - - - = it will never be activated)

(7)

Hd6 0.0

23.5 h.damin

(6)

- - -

sixth defrost activation time (it is important if dE = 3; - - - = it will never be activated)

(7)

10.3 Second level parameters

LABEL MIN. MAX. U.M.

DEF. MEASURE INPUTS

/0

1

3

---

1

kind of probe (1 = PTC, 3 = NTC)

/1A

-10

10.0 °C/°F

(5)

0.0

cabinet probe calibration

/1b

-10

10.0 °C/°F

(5)

0.0

evaporator probe calibration

/5

0

1

---

1

temperature resolution (it is important if /8 = 1; 0 = 1 degree, 1 = 0.1 degrees)

/8

0

1

---

1

temperature unit of measure (0 = Fahrenheit degree, 1 = Celsius degree)

LABEL MIN. MAX. U.M.

DEF. REGULATOR

r0

0.1

15.0 °C/°F

(5)

2.0

hysteresis (differential, it is relative to the working setpoint)

r1

-99

r2

°C/°F

(5)

-50

minimum value you can assign to the working setpoint

r2

r1

99.9 °C/°F

(5)

50.0 maximum value you can assign to the working setpoint

r5

0

1

---

0

working setpoint modification lock-out (1 = YES)

r8

-99

99.9 °C/°F

(5)

0.0

auxiliary working setpoint (it is the working setpoint during the multifunction input activa-

tion if i0 = 6 or 7 and during the Energy Saving cycle)

LABEL MIN. MAX. U.M.

DEF. COMPRESSOR PROTECTION

C0

0

240

min

0

minimum delay between you turn the instrument ON and the first compressor activation

C1

0

240

min

5

minimum delay between two compressor activation in succession

C2

0

240

min

3

minimum delay between the compressor gets OFF and the following activation

C4

0

1

---

0

fixed delay since the compressor gets ON and OFF (1 = YES, for 3 s)

C5

1

240

min

10

cycle time for the compressor activation during the cabinet probe alarm

C6

0

100

%

50

percentage of C5 the compressor is ON during the cabinet probe failure

(8)

LABEL MIN. MAX. U.M.

DEF. DEFROST

d0

0

99

h

8

defrost interval (it is important if dE ≠ 3); look at dE as well

(7)

(0 = the defrost will never

automatically be activated)

d1

0

1

---

1

kind of defrost (0 = electric defrost, 1 = hot gas defrost)

d2

-99

99.9 °C/°F

(5)

2.0

defrost end temperature (evaporator temperature)

d3

0

99

min

30

defrost maximum length (0 = the defrost will never be activated)

d4

0

1

---

0

defrost activation every time you turn the instrument ON (1 = YES)

(7)

d5

0

99

min

0

delay between you turn the instrument ON and the defrost activation (it is important if

d4 = 1)

d6

0

1

---

1

freeze of the temperature showed by the instrument during the defrost (1 = YES)

(9)

d7

0

15

min

2

dripping time

d9

0

1

---

0

compressor protections cleaning at the moment of the defrost activation (it is important if

d1 = 1; 1 = YES)

dE

0

3

---

0

defrost interval count mode; look at d0 as well (0 = the instrument counts the working time,

1 = the instrument counts the sum of the times the compressor is ON,

2 = the instrument counts the sum of the times the evaporator temperature is below dF,

3 = real time defrost, the defrost will be activated at the times you have set with the param-

eters Hd1 ... Hd6)

dF

-99

99.9 °C/°F

(5)

0.0

defrost interval count freeze threshold (evaporator temperature, it is important if dE = 2)

dP

0

99

min

0

minimum time the compressor must have been ON at the moment of the defrost activation

in order that the defrost can be activated (it is important if d1 = 1)