Appendix 5: Profibus DP / ProfiNet Data Structure (FT-11 only)

The output from FT-11 on PLC requests is in four words and according to the table below.

FT-11 Output

Bit no.

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

0

1

st

Word

W31

MSB

W30 W29 W28 W27 W26 W25 W24 W23 W22 W21 W20 W19 W18 W17

W16

2

nd

Word W15 W14 W13 W12 W11 W10 W9 W8 W7 W6 W5 W4 W3 W2 W1

W0

LSB

3

rd

Word

Error

0 MR In3 In2 In1 Out3 Out2 Out1

0 Net MT

Data

Ok

Data

Integrity

4

th

Word

Not in use


Here the first and the second word provide the weight information (32-bit signed integer or 32-bit signed floating
point, see chapter 8.4.2 respective 8.5.2; WXX = Weight bit XX; W31 = MSD; W0 = LSD ) and the third word is
the status as indicated below.

Bit no.

3

rd

Word

Description in normal operation

15

14

13

Error

000

No error

001 ADC

out

010 ADC

over

011 ADC

under

100 System

error

101

FT-11 not in weighing mode

12

Not Used

Always 0

11

MR

Single Range: always 0

Multi Range: 1. Range = 0 2. Range = 1

10

Digital Input 3

9

Digital Input 2

8

Digital Input 1

Input bit status ( Active = 1 )

7

Digital Output 3

6

Digital Output 2

5

Digital Output 1

Output bit status ( Active = 1 )

4

Not Used

Always 0

3

Net

0: Gross Mode; 1: Net Mode

2

Motion

0: Motion ; 1: No Motion

1

Data Ok

0: Check the error bits; 1: Scale is operating properly

0

Data update in
progress

0: PLC should not use the data; 1: use the data
(if 0, the instrument was updating the PLC interface shared memory while data was
read. The PLC interface should ignore this data and rescan.)

Bit no.

3

rd

Word

Description during the calibration

0000 0001

Calibration Timeout –
Restart calibration

0000 0010

ADC Error
– Re-energize the instrument
– If seen again, change board.

0000 0011

Instrument cannot be calibrated
– Check load cell cable
– Re-energize the instrument

0010 0010

Instrument cannot be calibrated
– Load cell signal is too low or too high

0010 0011

Calibration Error
– Calibration test weight is too small, increase calibration weight
– Check load cell connections

0010 0101

Scale unstable
– Wait until scale becomes stable
– Check grounding wiring

15 … 8

Calibration error

0010 0110

Calibration Jumper is not installed- Check Calibration jumper

0000 0001

Ready for calibration

0000 0011

Zero calibration in process

0000 0100

Span calibration in process

7...0 Calibration

status

0000 1001

Calibration error (see bit 15...8)