3. Operation

There are 2 LEDs and 3 keys on the front panel of FAA-25. The

keys are used for setup and adjustments and the LEDs have
different meaning in operation and setup mode. The usage of the
keys is described in chapter 4.


In operation mode with connected electrical load the green RUN

LED is on and the red ERROR LED is off. See chapter 6 in case of
the red LED turns on.

The status of the LEDs during normal operation is given in the table
below.

In normal operation

0 – 10 V output

4 – 20 mA output

Green RUN LED

Flashes (on for 4 seconds)

On

Red ERROR LED

Off

Off

For troubleshooting see chapter 6.

The analogue output signal gives information about the status of the system and the weighing process:

Condition

0 – 10 V output

4 – 20 mA output

Error (option)

Operation X

X

High

Setup X

X

Low

Weight is higher than the range (Over)

13 V

24 mA

Low

Weight is lower than the zero range (Under)

-1.4 V

0 mA

Low

System Error

13 V

24 mA

Low

ADC is out of operating range

-1.4 V

0 mA

Low

4.

Setup and Calibration by using the Key Buttons

During the power on period the green and red LEDs are lightened for 3 seconds. After both LEDs turned off for
a short period, one of them will be lightened. If you did not follow this LED signalization sequence, power off the
instrument, check the power and the load cell cables and power it on again.
In this step the lightened LED informs you about the active analogue output mode of the instrument. If the green
RUN LED is continuously lightened, the analogue output mode is 4 – 20 mA; if it flashes, the analogue output
mode is 0 – 10 V (the electrical load should be connected before). If the planned usage is different from the
active mode, you have to select the analogue output mode first, see Chapter 4.1.
After this the instrument is set up and calibrate as described in Chapter 4.2.
Finally check the performance of your system with different test weights. After being sure of the accuracy of the
system you can use it.

4.1. Setup of the Analogue Output Mode

The selected analogue output mode (voltage or current) is indicated by the RUN LED and the ERROR LED as
described in chapter 3.

If you want to change the analogue output mode press

and

keys simultaneously.

If you have changed the analogue output mode, you have to recalibrate the transmitter – regardless if it
has already been calibrated for the other output mode.

4.2. Setup and Calibration

Warning: The analogue output mode shall be selected as 0 – 10 V or 4 – 20 mA before the calibration.
Do not forget to calibrate the instrument after changing the analogue output mode.
In this chapter you will find the required information for the setup and the calibration of FAA-25. The symbols at
the right bottom of the keys show the function of the keys in setup mode. The meanings of the keys in the setup
mode are given in the table below.

Enter / exit the setup mode

Go to the next step

 Save

Increase the value

Setup Setpoint no. 1

Filter type “High”

Decrease the value

Setup Setpoint no. 2

Filter type “Low”