FloAire PCU Filtration User Manual

Page 14

Advertising
background image

14

Troubleshooting

The following table lists causes and corrective actions for possible faults shown on the HMI with the
Pollution Control Units. Review this list prior to consulting manufacturer.

Fault

Potential Cause

Corrective Action

Calibration Required

Unit not calibrated upon start up

Calibrate the PCU

Unit taking too long to calibrate

Varying airflow at inlet of the PCU

Check for blocked PORT 8

(Atmospheric port)

Ftlr Clogged

Filters in a module are clogged

Replace filters in module showing

“100% Clog” with clean filters of

the same filter type

Access door in duct left open

Close access door in duct

Ftlr Missing

Filters in a module are missing

Place filters back in Missing Filter

module and check for missing

filters in all other modules

Hood filters are clogged

Clean filters in the hood

Blocked Inlet to the PCU

Make sure nothing is blocking air

flow entering the PCU

PCU clogged

Pressure drop across entire PCU

exceeds allowable limits

Replace filters in module showing

maximum percentage clog with

clean filters of same type

Access door in duct left open

Close access door in duct

72hr Clog

Filters in a module are clogged for

72 hours

Replace filters in module showing

“100% Clog” with clean filters of

the same filter type

Pressure drop across entire PCU

exceeds allowable limits for 72

hours

Replace filters in module showing

maximum percentage clog with

clean filters of same type

Access door in duct left open for

72 hours

Close access door in duct

Missing Door

Missing Door in one of the

modules

Place door back in module having

missing door and check for

missing filters in each module



ATTENTION!!

In order to prevent erroneous issuing of fault conditions, the monitoring system takes

several minutes to issue a fault.

FAULTS will not be detected if PCU is running outside Normal Hood operating

conditions.