Troubleshooting

The following table lists causes and corrective actions for possible problems with the pollution control
units and the fan attached to the PCU. Review this list prior to consulting manufacturer.

Troubleshooting Chart

Problem

Potential Cause

Corrective Action

Fan Motor Overload / Excessive

Airflow

Filters not installed

Install all filters and unit doors

Fan speed is too high

Reduce fan RPM

Motor wired incorrectly

Check motor wiring to wiring

diagram located on fan motor

Overload in starter set too low

Set overload to motor FLA value

Motor HP too low

Determine if HP is sufficient for job

Duct static pressure lower than design

Reduce fan RPM

Insufficient Airflow

Fan rotating in the wrong direction

Be sure fan is rotating in the

direction shown on rotation label

Poor outlet conditions

There should be a straight clear duct

at the outlet

Duct static pressure higher than design

Improve ductwork to eliminate or

reduce duct losses

Blower speed too low

Increase fan RPM. Do not overload

motor

Dirty or clogged filters

Clean and/or replace

Belt slippage

Adjust belt tension

Excessive Vibration and Noise

Misaligned pulleys

Align pulleys

Damaged or unbalanced wheel

Replace wheel

Fan is operating in the unstable region

of the fan curve

Refer to performance curve for fan

Bearings need lubrication or

replacement

Lubricate or replace

Fan speed is too high

Reduce fan RPM

Belts too loose, worn or oily

Inspect and replace if needed

Check PCU filter light is ON

Air Pressure Switch Option

Clean and/ or replace filters

Dirty or clogged filters

Switch set incorrectly

Set switch to .15” w.c. above internal

pressure of clean PCU

Internal static pressure is higher than

estimated

Increase switch setting by .1” w.c.

Advanced Filter Monitoring Option

See Page 12 for details

Fault shown on HMI screen

Check PCU light does NOT come

on

Light is burned out

Check light with jumper wire, check

related wiring, replace/ repair if

needed

Switch is set incorrectly

Set switch to .15” w.c. above internal

pressure of clean PCU

Internal static pressure is lower than

estimated

Decrease switch setting by .1” w.c.

Fan and Cooking Equipment will

not operate

PCU Missing Door

See page 12 for details

PCU Missing Filters

PCU Filters Clogged for 72 hours

Sounding of Audible Alarm

PCU filters clogged for 24 hours

Replace Clogged filters with clean

filters of same type

Smoke/Odor leaking from PCU

Exhaust fan installed before PCU

Move exhaust fan to discharge side

of the PCU