Fig. 8—ac or 1-stage system wiring diagram, Fig. 9—hp or 2-stage system wiring diagram – Carrier ZONECC3Z User Manual

Page 5

Advertising
background image

Connect the equipment R to both Rz and either Rh or Rc. A jumper
will be needed. Rc and Rh are internally connected but may be
separated by breaking a twist-off (see step 4 below).

Step 3—Wire Dampers

Each damper has three connections: Close, Open, and Common.
Find the connection points along the lower left side of the 3-Zone
Control. Suggested colors are Close = red; Open = green; Common
= white. Field label and make the connections at the dampers and
at the 3-Zone Control. Be careful not to cross zone numbers.

Step 4—Wire Remainder

Connect the LAT sensor to the LAT and LATC terminals. Polarity
does not matter. If used, connect the HPT sensor to the HPT and
HPTC terminals. If the HPT sensor is not used, you must leave the
10K ohm resistor connected in its place.

If the cooling and heating systems have separate transformers,
twist off the Rc/Rh jumper using a pair of long nosed pliers. Then
connect the R of the cooling transformer to Rc, the R of the heating
transformer to Rh and the common of both transformers to C.
Connect a jumper wire between Rz and Rc. Rc powers G, Y, and
O outputs. Rh powers W outputs.

Fig. 8—AC or 1-Stage System Wiring Diagram

A04192

Rh
Rc

Y1
W1

G

R

C

Y1
W1

G

R

C

Y1
W1

G

R

C

Y1
W1

G

CLS_1
COM_1

OPN_1

CLS

_ 2

COM_2

OPN _ 2

CLS

_ 3

COM_3

OPN _ 3

C

Rz

LATC

LAT

ON

1 2 3 4 5 6 7

Relay

Relay

Relay

Fuse

Triac

Triac

Triac

Triac

Triac

Triac

Power Supply

Micro

W

Y1

G

Damper 1

Damper 2

Damper 3

Compressor

Timer Override

Status

Rc/Rh

Twist Of f

Zone

Zone

Zone

Dipswitches 1- 8

To 24VAC
Power

To Equipment

To Zone 1
Damper

To Zone 2
Damper

To Zone 3
Damper

To LAT
Sensor

To

Zo

ne

Thermostat

To

Zon

e

Thermostat

To Zone
Thermostat

Programming

Connecto

r

Fig. 9—HP or 2-Stage System Wiring Diagram

A04191

Rh

Rc

Y1
W1

G

Y2

W2

O

R

C

Y1
W1

G

Y2

W2

O

R

C

Y1
W1

G

Y2

W2

O

R

C

Y1
W1

G

Y2

W2

O

CLS_1
COM_1

OPN_1

CLS 2
COM_2

OPN 2

CLS 3
COM_3

OPN 3

C

R

HPT

HP

LATC

LAT

ON

1 2 3 4 5 6 7

1 2 3

ON

Relay

Relay

Relay

Relay

Relay

Relay

Fuse

Triac

Triac

Triac

Triac

Triac

Triac

Power Supply

Micro

W

Y1

G

W

Y2

O

Damper 1

Damper 2

Damper 3

Compressor

Timer Override

E-Heat

Status

E-Heat

Rc/R

Twist Of f

Zone

Zone

Zone

To Zone 1
Thermostat

To Zone 2
Thermostat

To Zone 3
Thermostat

To 24VAC
Power

To
Equipment

To Zone 1
Damper

To Zone 2
Damper

To Zone 3
Damper

To HPT
Sensor

To LAT
Sensor

Dipswitches 1 - 12

Connector

Prog

ramming

5