High Temperature Limit

High Temperature Limit

One of the back up safety device is the

high temperature limit switch.

This switch is a mechanical thermostat that measures the temperature
inside the unit downstream of the burner. If the factory-set temperature
of 180°F is exceeded, it will signal the FSC to turn off the burner. This
requires a manual reset of the high temperature limit. This insures that
the discharge does not exceed 185°F.

Operation Summary

With the blower already running and the airflow switch proven;

The outside air temperature falls below the setting of intake air thermostat

or

The optional remote panel is set to “Manual” and “Heat” mode

The FSC in energized and the following occurs;

FSC indicates that it has power

FSC verifies proper Airflow

Begins a 15 second Pilot Trial For Ignition

The pilot gas solenoid valve is opened, the spark igniter begins sparking, and the flamerod
sensor watches for flame initiation

When flame is established, the main valve opens and the FSC powers the Maxitrol system
and gas flow begins modulating

The FSC monitors the flame while the Maxitrol system adjusts to the selected temperature

The Maxitrol system checks the discharge air temperature (and the room temperature for the Maxitrol
44) and regulates the gas going to the burner to satisfy the temperature setting. The Maxitrol system
will modulate the main burner gas from 100% down to 5% as needed.