Warning, Caution, Installation – FloAire Baset Series User Manual

Page 2: Check equipment and job site, Install on a solid, level mounting pad, Clearance requirements, Operating ambient, Make piping connections

Advertising
background image

2

INSTALLATION

Check Equipment and Job Site

UNPACK UNIT
Move to final location. Remove carton taking care not to damage

unit.

Inspect Equipment

File claim with shipping company prior to installation if shipment
is damaged or incomplete. Locate unit rating plate on unit corner

panel. It contains information needed to properly install unit.
Check rating plate to be sure unit matches job specifications.

Install on a Solid, Level Mounting Pad

If conditions or local codes require the unit be attached to pad, tie

down bolts should be used and fastened through knockouts
provided in unit base pan. Refer to unit mounting pattern in Fig. 2

to determine base pan size and knockout hole location.
For hurricane tie downs, contact local distributor for details and PE

(Professional Engineer) certification, if required by local

authorities.
On rooftop applications, mount on level platform or frame. Place

unit above a load--bearing wall and isolate unit and tubing set from
structure. Arrange supporting members to adequately support unit

and minimize transmission of vibration to building. Consult local
codes governing rooftop applications.
Roof mounted units exposed to winds may require wind baffles.

Consult the Application Guideline and Service Manual --
Residential Split System Air Conditioners and Heat Pumps for

wind baffle construction.
NOTE: Unit must be level to within ±2_ (±3/8 in./ft ,.±9.5 mm/m)

per compressor manufacturer specifications.

Clearance Requirements

When installing, allow sufficient space for airflow clearance,

wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm)
clearance to service end of unit and 48 in. (1219.2 mm) (above

unit. For proper airflow, a 6--in. (152.4 mm) clearance on 1 side of
unit and 12--in. (304.8 mm) on all remaining sides must be

maintained. Maintain a distance of 24 in. (609.6 mm) between

units or 18 in. (457.2 mm) if no overhang within 12 ft. (3.66 m)
Position so water, snow, or ice from roof or eaves cannot fall

directly on unit.
NOTE: 18” (457.2 mm) clearance option described above is
approved for outdoor units with wire grille coil guard only.
Units with louver panels require 24” (609.6 mm) between units.
On rooftop applications, locate unit at least 6 in. (152.4 mm) above

roof surface.

Operating Ambient

The minimum outdoor operating ambient in cooling mode without
accessory is 55 _F (12.78 _C), and the maximum outdoor

operating ambient in cooling mode is 125_F (51.67 _C).

Make Piping Connections

!

WARNING

PERSONAL INJURY AND ENVIRONMENTAL

HAZARD
Failure to follow this warning could result in personal injury or

death.
Relieve pressure and recover all refrigerant before system

repair or final unit disposal. Use all service ports and open all

flow--control devices, including solenoid valves.
Federal regulations require that you do not vent refrigerant to

the atmosphere. Recover during system repair or final unit

disposal.

CAUTION

!

UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment

damage or improper operation.
If ANY refrigerant tubing is buried, provide a 6--in. vertical

rise at service valve. Refrigerant tubing lengths up to 36--in.

may be buried without further special consideration. Do not

bury lines more than 36--in. (914.4 mm).

3/8---in. (9.53 mm) Dia.

Tiedown Knockouts in

Basepan(2) Places

View From Top

UNIT BASE PAN

Dimension in. (mm)

TIEDOWN KNOCKOUT LOCATIONS in. (mm)

A

B

C

23---1/2 X 23---1/2

(596.9 X 596.9)

7---13/16 (198.4)

4–7/16 (112.7)

18–1/16 (458.8)

26 X 26

(660.4 X 660.4)

9–1/8 (231.8)

4–7/16 (112.7)

21–1/4 (539.8)

31–1/2 X 31–1/2

(800.1 X 800.1)

9–1/8 (231.8)

6–9/16 (166.7) 24–11/16 (627.1)

35 X 35

(889 X 889)

9–1/8 (231.8)

6–9/16 (166.7)

28–7/16 (722.3)

A05177

Fig. 2 -- Tiedown Knockout Locations

Outdoor units may be connected to indoor section using accessory

tubing package or field--supplied refrigerant grade tubing of correct
size and condition. Rated tubing diameters shown in Table 1 are

recommended up to 80 ft. (24.38 m). See Product Data for
acceptable alternate vapor diameters and associated capacity losses.

For tubing requirements beyond 80 ft. (24.38 m), substantial

capacity and performance losses can occur. Following the
recommendations in the Longline Guideline will reduce these

losses. Refer to Table 1 for field tubing diameters. Refer to Table 2
for accessory requirements.
There are no buried--line applications greater than 36--in. (914.4

mm) allowed.
If refrigerant tubes or indoor coil are exposed to atmosphere, they

must be evacuated to 500 microns to eliminate contamination and
moisture in the system.

Outdoor Unit Connected to Factory Approved Indoor

Unit

Outdoor unit contains correct system refrigerant charge for

operation with factory approved AHRI rated indoor unit when
connected by 15 ft. (4.57 m) of field--supplied or factory--accessory

tubing, and factory supplied filter drier. Check refrigerant charge

for maximum efficiency.

Refrigerant Tubing Connection Outdoor

Connect vapor and liquid tubes to fittings on vapor and liquid

service valves (see Table 1.) Use refrigerant grade tubing

24AB

B

Advertising