Sweat Connection

CAUTION

!

UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment

damage or improper operation.
Service valves must be wrapped in a heat--sinking material

such as a wet cloth while brazing.

Use refrigeration grade tubing. Service valves are closed from

factory and ready for brazing. After wrapping service valve with a
wet cloth, braze sweat connections using industry accepted

methods and materials. Consult local code requirements.
Refrigerant tubing and indoor coil are now ready for leak testing.

This check should include all field and factory joints.

Table 1 – Refrigerant Connections and Recommended Liquid

and Vapor Tube Diameters (In.)

24ABB3

UNIT SIZE (SERIES)

LIQUID

RATED VAPOR*

Connection

& Max. Tube

Diameter

Connection

Diameter

Tube

Diameter

18, 24 (Series 0)

3/8

5/8

5/8

18, 24 (Series 1)

3/8

3/4

3/4

30

3/8

3/4

3/4

36 (Series 0)

3/8

3/4

3/4

36 (Series 1)

3/8

7/8

7/8

42, 48

3/8

7/8

7/8

60

3/8

7/8

1---1/8

24ABB4

UNIT SIZE (SERIES)

LIQUID

RATED VAPOR*

Connection

& Max. Tube

Diameter

Connection

Diameter

Tube

Diameter

18, 24

3/8

5/8

5/8

30, 36

3/8

3/4

3/4

42, 48, 49

3/8

7/8

7/8

60, 61

3/8

7/8

1---1/8

* Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for

performance data when using different size and length linesets.

Notes:

1. Do not apply capillary tube or fixed orifice indoor coils to these units.
2. For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m)

horizontal or 35 ft. (10.7 m) vertical differential 250 ft. (76.2 m) Total

Equivalent Length), refer to the Residential Piping and Longline Guide

line--- Air Conditioners and Heat Pumps using Puron refrigerant.

3. For alternate liquid line options on 18---42 size units, see Product Data or

Residential Piping and Application Guideline

Install Liquid--Line Filter Drier Indoor

CAUTION

!

UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment

damage or improper operation.
1. Installation of filter drier in liquid line is required.
2. Filter drier must be wrapped in a heat--sinking material

such as a wet cloth while brazing.

Refer to Fig. 3 and install filter drier as follows:

1. Braze 5--in. liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to above 5--in. (127 mm) liquid tube.

Flow arrow must point towards indoor coil.

4. Connect and braze liquid refrigerant tube to the filter drier.

A05178

Fig. 3 -- Liquid Line Filter Drier

Evacuate Refrigerant Tubing and Indoor Coil

CAUTION

!

UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment

damage or improper operation.
Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor coil should be evacuated using the

recommended deep vacuum method of 500 microns. The alternate
triple evacuation method may be used (see triple evacuation

procedure in service manual). Always break a vacuum with dry
nitrogen.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of

pulling a vacuum of 500 microns and a vacuum gage capable of
accurately measuring this vacuum depth. The deep vacuum method

is the most positive way of assuring a system is free of air and
liquid water. A tight dry system will hold a vacuum of 1000

microns after approximately 7 minutes. See Fig. 4.

500

MINUTES

0

1

2

3

4

5

6

7

1000

1500

LEAK IN

SYSTEM

VACUUM TIGHT

TOO WET
TIGHT

DRY SYSTEM

2000

MI

CRONS 2500

3000

3500

4000

4500

5000

A95424

A95424

Fig. 4 -- Deep Vacuum Graph

Final Tubing Check

IMPORTANT: Check to be certain factory tubing on both indoor
and outdoor unit has not shifted during shipment. Ensure tubes are
not rubbing against each other or any sheet metal or wires. Pay
close attention to feeder tubes, making sure wire ties on feeder
tubes are secure and tight.

24AB