REFRIGERANT PIPING LENGTH LIMITATIONS

Maximum Line Lengths:

The maximum allowable total equivalent length for heat pumps varies depending on the vertical separation. See the tables below for

allowable lengths depending on whether the outdoor unit is on the same level, above or below the outdoor unit.

Maximum Line Lengths for Heat Pump Applications

MAXIMUM ACTUAL LENGTH

ft (m)

MAXIMUM EQUIVALENT LENGTH{

ft (m)

MAXIMUM VERTICAL

SEPARATION ft (m)

Units on equal level

200 (61)

250 (76.2)

N/A

Outdoor unit ABOVE

indoor unit

200 (61)

250 (76.2)

200 (61)

Outdoor unit BELOW

indoor unit

See Table ’Maximum Total Equivalent Length: Outdoor Unit BELOW Indoor Unit’

{

Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.

Maximum Total Equivalent Length

{

-- Outdoor Unit BELOW Indoor Unit

Size

Liquid Line

Diameter

w/ TXV

HP with Puronr Refrigerant --- Maximum Total Equivalent Length{

Vertical Separation ft (m) Outdoor unit BELOW indoor unit;

0---20

(0 --- 6.1)

21---30

(6.4 --- 9.1)

31---40

(9.4 --- 12.2)

41---50

(12.5 --- 15.2)

51---60

(15.5 --- 18.3)

61---70

(18.6 --- 21.3)

71---80

(21.6 --- 24.4)

18000

HP with

Puron

3/8

250*

250*

250*

250*

250*

250*

250*

24000

HP with

Puron

3/8

250*

250*

250*

250*

250*

250*

250*

30000

HP with

Puron

3/8

250*

250*

250*

250*

250*

250*

250*

36000

HP with

Puron

3/8

250*

250*

250*

250*

250*

250*

250*

42000

HP with

Puron

3/8

250*

250*

250*

250*

250*

250*

150

48000

HP with

Puron

3/8

250*

250*

250*

250*

230

160

--- ---

60000

HP with

Puron

3/8

250*

225*

190

150

110

--- ---

--- ---

* Maximum actual length not to exceed 200 ft (61 m)

{

Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.

--- --- = outside acceptable range

LONG LINE APPLICATIONS

An application is considered Long Line when the refrigerant level in the system requires the use of accessories to maintain acceptable
refrigerant management for systems reliability. Defining a system as long line depends on the liquid line diameter, actual length of the tubing,

and vertical separation between the indoor and outdoor units.
For Heat Pump systems, the chart below shows when an application is considered Long Line. Beyond these lengths, long line accessories

are required:

HP WITH PURONr REFRIGERANT LONG LINE DESCRIPTION ft (m)

Beyond these lengths, long line accessories are required

Liquid Line Size

Units On Same Level

Outdoor Below Indoor

Outdoor Above Indoor

3/8

80 (24.4)

20 (6.1) vertical or 80 (24.4) total

80 (24.4)

Note:

See Long Line Guideline for details