Accessory usage guideline – FloAire 25HCD3 User Manual

Page 6

Advertising
background image

6

ACCESSORY USAGE GUIDELINE

Accessory

REQUIRED FOR LOW---AMBIENT

COOLING APPLICATIONS

(Below 55

F / 12.8C)

REQUIRED FOR

LONG LINE APPLICATIONS*

REQUIRED FOR

SEA COAST APPLICATIONS

(Within 2 miles / 3.22 km)

Accumulator

Standard

Standard

Standard

Ball Bearing Fan Motor

Yes{

No

No

Compressor Start Assist Capacitor and

Relay

Yes

Yes

No

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Hard Shutoff TXV

Yes

Yes

Yes

Isolation Relay

Yes

No

No

Liquid Line Solenoid Valve

No

See Long---Line Application Guideline

No

Motor MasterControl or

Low Ambient Switch

Yes

No

No

Support Feet

Recommended

No

Recommended

* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Split---System Longline

Application Guideline.

{

Additional requirement for Low---Ambient Controller (full modulation feature) MotorMasterr Control.

Accessory Description and Usage (Listed Alphabetically)

1. Ball--Bearing Fan Motor
A fan motor with ball bearings which permits speed reduction

while maintaining bearing lubrication.

Usage Guideline:

Required on all units when using MotorMasterr

2. Compressor Start Assist -- Capacitor and Relay
Start capacitor and relay gives a ”hard” boost to compressor motor

at each start up.

Usage Guideline:

Required for reciprocating compressors in the following

applications:

Long line
Low ambient cooling
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil

Required for single--phase scroll compressors in the
following applications:

Long line
Low ambient cooling

Suggested for all compressors in areas with a history of

low voltage problems.
3. Compressor Start Assist — PTC Type
Solid state electrical device which gives a ”soft” boost to the
compressor at each start--up.

Usage Guideline:

Suggested in installations with marginal power supply.

4. Crankcase Heater
An electric resistance heater which mounts to the base of the
compressor to keep the lubricant warm during off cycles. Improves

compressor lubrication on restart and minimizes the chance of
liquid slugging.

Usage Guideline:

Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.

5. Evaporator Freeze Thermostat
An SPST temperature--actuated switch that stops unit operation
when evaporator reaches freeze--up conditions.

Usage Guideline:

Required when low ambient kit has been added.

6. Isolation Relay
An SPDT relay which switches the low--ambient controller out of

the outdoor fan motor circuit when the heat pump switches to
heating mode.

Usage Guideline:

Required in all heat pumps where low ambient kit has
been added.

7. Liquid--Line Solenoid Valve (LLS)
An electrically operated shutoff valve which stops and starts

refrigerant liquid flow in response to compressor operation. It is to

be installed at the outdoor unit to control refrigerant off cycle
migration in the heating mode.

Usage Guideline:

An LLS is required in all long line heat pump

applications to control refrigerant off cycle migration in

the heating mode. See Long Line Guideline.

8. Low--Ambient Pressure Switch Kit
A long life pressure switch which is mounted to outdoor unit
service valve. It is designed to cycle the outdoor fan motor in order

to maintain head pressure within normal operating limits. The
control will maintain working head pressure at low--ambient

temperatures down to 0_F (--18_C) when properly installed.

Usage Guideline:

A Low--Ambient Pressure Switch or MotorMasterr

Low--Ambient Controller must be used when cooling
operation is used at outdoor temperatures below 55_F

(12.8_C).

9. MotorMasterr Low--Ambient Controller
A fan--speed control device activated by a temperature sensor,

designed to control condenser fan motor speed in response to the
saturated, condensing temperature during operation in cooling

mode only. For outdoor temperatures down to --20_F (--28.9_C), it

maintains condensing temperature at 100_F 10_F (37.8_C 

6.5_C).

Usage Guideline:

A MotorMasterr Low Ambient Controller or

Low--Ambient Pressure Switch must be used when
cooling operation is used at outdoor temperatures

below 55_F (12.8_C).

Suggested for all commercial applications.

25H

C

D

3