BLOWER  /  MOTOR  SECTION  

Unit(s)   shall   be   supplied   with   a   single   AMCA   rated   centrifugal   backward   inclined   insdustrial  
statically   and   dynamically   balanced   blower.   The   fan   shall   be   mounted   on   a   heavy   duty   machined  
and   polished   shaft.   The   shafts   maximum   operating   speed   is   not   to   exceed   75%   of   its   first   critical  
speed.   The   bearings   and   motor   shall   be   mounted   in   the   airstream.   The   T-­‐frame   motor   shall   be  
mounted   in   a   motor   compartment   on   a   fully   adjustable   base.   The   bearings   are   to   be   industrial  
pillow   block   type   supplied   with   extended   grease   lines.   The   blower   is   to   be   driven   with   an  
(adjustable)  (fixed)  1.25  s.f.  V-­‐belt  drive  package  concealed  in  a  belt  guard.  Outdoor  units  shall  have  
hinged  door(s)  to  provide  easy  access  to  maintain  and  inspect  motor,  belts  &  bearings.  

 
BURNER  SECTION  

Each  unit  shall  be  equipped  with  a  wide  range  fully  modulating  direct  gas-­‐fired  burner  capable  of  
30:1   turndown.   The   burner   shall   have   stainless   steel   combustion   baffles,   non-­‐clogging   gas   ports,  
spark-­‐ignited  intermittent  pilot  and  flame  safeguard  system.  Burner  combustion  must  be  clean  and  
odorless.   Combustion   efficiency   must   limit   the   products   of   combustion   to   a   maximum   of   5   ppm  
carbon   monoxide   and   0.5   ppm   nitrogen   dioxide.   The   burner   profile   is   to   be   equipped   with  
adjustable   profile   plates.   A   heat   treated   glass   observation   port   shall   provide   a   full   view   of   flame.  
Hinged   access   door(s)   are   to   be   provided   to   allow   easy   maintaince   and   inspection   for   burner,  
ignitor  and  flamerod.  

 

CONTROL/MANIFOLD  COMPARTMENT  

Unit  control  enclosure  to  have  hinged  access.  Terminal  strip  and  all  wiring  shall  be  numbered.  The  
controls  for  the  heater  shall  include;  

 

blower  motor  starter  w/ambient  compensated  overloads  and  auxiliary  contact(s).  

 

primary  to  120v  control  transformer  

 

6,ooo  volt  ignition  transformer  

 

control  circuit  breaker  and  service  switch  

 

manual  reset  temperature  high  limit  

 

flamesafeguard  relay  w/  LED  status  and  flamerod  

 

discharge  temperature  control  sensor  

 

differential  air  proving  safety  switch  

 

automatic  low  temperature  limit  (optional)  

All  wiring  external  to  control  enclosure  shall  be  run  in  conduit.  The  gas  manifold  shall  include;  

 

main  gas  pressure  regulator  

 

high  gas  pressure  regulator  (optional)  

 

manual  shutoff  &  test  firing  valve  

 

main  gas  automatic  shutoff  valve  

 

auxiliary  main  gas  automatic  shutoff  valve  

 

modulating  control  system  

 

pilot  pressure  regulator  

 

pilot  automatic  shutoff  valve  

 

pilot  manual  shutoff  valve  

 

pilot  needle  valve  

 

multiple  test  ports  