Figure 3. Set point Adjustment Components and Locations

A.

Establish a flow rate at the desired trip point. The relay in standard flow switches is picked
up (energized) when the flow level is above a set point. A low level is therefore indicated in
the event of loss of power to the sensor when connected to N.C. contacts. Relay 2 will be
energized with flow below the trip level.

B.

If RELAY2 is energized, adjust “Trip2” potentiometer counter clockwise until the relay de-
energizes. This is the alarm condition.

C.

If RELAY2 is de-energized, adjust “Trip2” slowly clockwise just until the relay energizes.

D.

If the relay cannot be made to drop out over the full range of the “Trip2” potentiometer, see
Table III.

TABLE I. Alarm1 Output Configuration (all Model 400 units)

S1 Position

NC1 - COM

contacts

Relay1 State

LED1 Status

Flow Rate

Liquid Level

LO

Open

energized

Green

Above set point

Liquid

LO

Closed

de-energized

Red

Below set point

Air

HI

Closed

de-energized

Red

Above set point

Liquid

HI

Open

energized

Green

Below set point

Air