Testing the reader, Removing the cover, Specifications – Interlogix T-100 User Manual

Page 2: Fcc compliance, Ordering information

Advertising
background image

Testing the reader

1. Power up the reader. Verify the power-on self

test LED/beep sequence:
- green LED flashes; two short beeps
- yellow LED flashes; three short beeps
- red LED flashes
- yellow LED flashes

2. Verify the yellow LED lights indicating the

reader is ready.

3. Present a badge that has been properly

enrolled in the system. Verify the green LED
lights and a short beep is heard.

Removing the cover

To remove the cover, squeeze the sides of the top
cover and pull to release the cover.

Specifications

The voltage specification for this reader is 5-16
VDC, although 12 VDC or greater is recommended
for better performance and cable run distances.
The recommended cable gauge is 18-gauge to 22-
gauge. Check with the cable supplier to determine
the best choice for the application and installation
distance.

FCC compliance

The FCC requires the following statement: This
reader uses radio frequency energy, has been
tested, and complies with the limits of FCC testing.
Changes, modifications, or disregard of proper
installation and instructions not expressly approved
by UTC Fire & Security are strictly prohibited by the
FCC and could void the user’s authority to operate
the equipment.

Ordering information

Note: Each part number includes all three colors of the
cover plates (black, charcoal, gray).

© 25JUL13, United Technologies Corporation

Interlogix is part of UTC Climate, Controls & Security, a
unit of United Technologies Corporation. All rights
reserved.

The TruPortal product name and logo are trademarks of
United Technologies. Other trade names used in this
document may be trademarks or registered trademarks
of the manufacturers or vendors of the respective
products.

Document number: 460949002C - July 2013

Colors

Black, Charcoal, Gray

Power supply

Linear DC recommended

Power usage

70 mA @ 12 VDC

Voltage range

5 - 16 VDC

Temperature
range

a

a. -25°F to 125°F (32°C to 52°C)

-31°F to 149°F (-35°C to 65°C)

Cable
distance to
panel

b

b. 500 ft. (152.4 m) max. 22 AWG @ 12 VDC

200 ft. (60.96 m) max. 22 AWG @ 5 VDC

Read Range

c

(Distances
may vary
depending on
environment.)

c. Proximity: up to 3.0" (7.62 cm)

HID Proximity: up to 3.0" (7.62 cm)

Proximity Perfect cards are not
supported by the TruPortal Series
reader.
- CASI ProxLite: up to 3.5" (8.89 cm)
- HID Proximity: up to 3.5" (8.89 cm)

Wiegand
output

d

d. HID Proximity/Corporate 1000: Most formats (up to

64-bit)

- Proximity: 4002 (40-bit) 12 digits
- HID Proximity/Corporate
1000: Most formats (26 to 174-bit)

Regulatory
approvals and
standards

UL 294, CE, and FCC Part 15

UL evaluation for UL Listed Installations:

Cable Distance
Max. @ 12 VDC

AWG

200 ft. (60.96 m)

22

300 ft. (91.44 m)

20

500 ft. (152.4 m)

18

Product

Part numbers

T-100
(3 covers, 18" / 45.7 cm pigtail wire)

TP-RDR-100a

T-100
(3 covers, 84" / 214 cm pigtail wire)

TP-RDR-100b

Advertising