Connecting the cable, Testing the reader, Removing the cover – Interlogix T-500 User Manual

Page 2

Advertising
background image

Figure 4. Aligning base plate and top cover

8. Verify the connection is secure and install the

security screws on the top and bottom of the
reader.

9. Cover the exposed screws with the rubber

plugs provided.

Figure 5. Gasket detail

Connecting the Cable

1. The readers are supplied with a 12-conductor

cable pigtail with drain wire. Connect the pigtail
to the host panel. Use the Cable Connection

Chart (below) to correctly match the color of
each wire.

Color

Signal

Red

6 to 16 VDC

Black

Ground

Green

Data 0

White

Data 1

Orange

Green LED Control

Brown

Red LED Control

Yellow

Beeper Control

Gray

Door DI

Pink

REX DI

Tan

Tamper Output

Blue

Hold

Purple

Reserved

........

Drain Wire

2. Use a DC Power source between 6-16 VDC.
3. Verify the reader is properly grounded by

attaching the ground wire to an earth ground
connection at the power supply or field panel
end of the cable. Connect reader’s drain wire
to the cable shield. Connect shield wires at the
field panel. The recommended cable gauge is
18-gauge to 22-gauge. Check with the cable
supplier to determine the best choice for the
application and installation distance.

Testing the Reader

1. Power up the reader. Verify the power-on self

test

LED/beep sequence:
- green LED flashes; two short beeps
- yellow LED flashes; three short beeps
- red LED flashes.
- yellow LED flashes.

2. Verify the yellow LED is on continously

indicating the reader is ready.

3. Present a badge that has been properly

enrolled in the system. Verify the yellow LED
flashes and a short beep is heard.

Removing the Cover

1. Remove all security screws.
2. Pull cover off the base. Refer to Figure 4 on

page 2.

Base plate

Top cover