Thermostat chart - hp – Coleman Echelon FC9V User Manual

Page 6

Advertising
background image

246786-CTG-B-0407

6

Unitary Products Group

Thermostat Chart - HP

HP24

Two Stage H/P - H*5B, YZE - w/Variable 2 Stage Furnace, 2 Stage Cooling Ready - PV8/9, (F,L)*8/9V, (G,L)*8/9V, XYG8V-*, XYF

8V-*, XYG9V-*, XYF9V-*

W/031-01996- Series Demand Control; Hot Heat Pump Mode OR Conventional

Thermostat Installer Setup Number 0200 -

Backup Heat Source - must be set to 1 - Heat

Pump Backup Heat Source is Fossil Fuel

Thermostat Installer Setup Number 0210 -

External Fossil Fuel Kit - must be set to 0 -

External Fossil Fuel Kit is Controlling Heat

Pump Backup Heat

Change FFuel Jumper on

Heat Pump to ON

Thermostat Installer Setup Number 0190 -

Reversing Valve (O/B) Operation - must be

set to 0 - O/B Terminal Energized in Cooling

Step 1 of Thermostat User

Configuration Menu must be

set to Heat Pump 2

E2/P Switch must be in the E2 position

and the Humidistat Jumper on CFM

Control must be in the 'YES' position for

Dehumidification

( ) CONVENIENCE TERMINAL. NO

FUNCTION IN THIS APPLICATION.

24V HUMIDIFIER

(Optional)

Thermostat Installer Setup Number 0170 -

System Type - must be set to

12 - 3 Heat/2 Cool Heat Pump

Selection of GAS/ELEC switch

on thermostat not necessary

Step 1 of Thermostat User Configuration

Menu must be set to Heat Pump 2

Set W2 Delay on furnace to OFF

HM

Humidistat

BSG

Bonnet Sensor

Bonnet Sensor (Optional)

BS

Bonnet Sensor

AUX

Auxiliary Heat

E/W1

First Stage Auxiliary Heat

E/W1

First Stage Auxiliary Heat

W

Auxiliary Heat

Y2

Second Stage Heat/Cool

DHM

Dehumidistat

HUM

Dehumidification - Open on Humidity Rise

Y2

Second Stage Heat/Cool

Y2

Second Stage Heat/Cool

Y2

Second Stage Heat/Cool

(Y 2)

O

Reversing Valve–Energized in Cool

L

Malfunction Light

L

Malfunction Light

L

Malfunction Light

(X/L)

Malfunction Light

X/L

Malfunction Light

O/B

Reversing Valve

O

Reversing Valve–Energized in Cool

O

Reversing Valve–Energized in Cool

(O)

Reversing Valve–Energized in Cool

CFM CONTROL

G

Fan

G

Fan

G

Fan

G

Fan

W1 OUT

First Stage Auxiliary Heat Output

W2

Second Stage Auxiliary Heat

W2

Second Stage Auxiliary Heat

W2

Second Stage Heat

W2 OUT

Second Stage Auxiliary Heat Output

E

Emergency Heat

W/W1

Single/First Stage Heat

Y2 OUT

Second Stage Cool Output

R

24-Volt Hot (Heat XFMR)

R

24-Volt Hot

R

24-Volt Hot

R

24-Volt Hot

R

24-Volt Hot

RC

24-Volt Hot (Cool XFMR)

Y/Y2

Single/Second Stage Cool

C

24-Volt Common

C

24-Volt Common

Y

First Stage Heat/Cool

Y1

First Stage Heat/Cool

Y1

First Stage Heat/Cool

Y1

First Stage Cool

Y1

First Stage Heat/Cool

*DP22U70124

*PP32U72124

C

24-Volt Common

C

24-Volt Common

C

24-Volt Common

TWO STAGE

HEAT PUMP

*PP32U70124

*DN22H00124

*PP32U71124

THERMOSTAT THERMOSTAT

T

HERMOSTAT

VARIABLE SPEED

FURNACE CONTROL

Advertising