Installation guidelines – Vermont Casting UC181N User Manual

Page 5

Advertising
background image

5

3311243

Fireplace Spacing Requirements

The illustration in Figure 2 shows spacing requirements
for your room with a hood installed (not included).

Without a hood, you must maintain a minimum of 32”
between the top opening of the firebox and the bottom
of a mantel which protrudes out 12”. If you do not have
at least 32” between the two, a hood must be installed.

With a hood installed, you must maintain a minimum
of 24” between the top opening of the fireplace and the
bottom of the mantel.

NOTE: The distance between any combustible
material and the top opening of the fireplace must
be a minimum of 18” above the opening.

Installation Guidelines

Minimum Fireplace Dimensions

A

B

C

D

Logset

Gas

Front

Rear

Min. Input

Max. Input

Width

Width

Depth

Height

BTU/Hr.

BTU/Hr.

18” - UC181N

29”

19”

14”

17”

25,000

39,000

18” - UE181N

29”

19”

14”

17”

25,000

39,000

24” - UC241N

Natural

29”

23”

14”

17”

25,000

39,000

24” - UE241N

29”

23”

14”

17”

25,000

39,000

18” - UC181L

29”

19”

14”

17”

25,000

39,000

18” - UE181L

29”

19”

14”

17”

25,000

39,000

24” - UC241L

Propane

29”

23”

14”

17”

25,000

39,000

24” - UE241L

29”

23”

14”

17”

25,000

39,000

The fireplace must meet the minimum dimensions listed below. (Fig. 1) Do not install the logset if the fireplace does
not meet these minimums.

A

B

D

C

FD370-2

Fig. 1 Minimum fireplace dimensions.

8"

Min.

12"

42"

6" Min.

18"

Min.

32"

Min.

12"

24"

Min.

Ceiling

Side Wall

Noncombustible
Material

Hood

Without Hood

Firebox
Opening

Noncombustible
Material

With Hood

Firebox
Opening

FP1498

Fig. 2 Clearances to combustibles.

NOTE: In all cases, the top of the
opening for the firebox must be a
minimum of 42” from the ceiling. The
side openings must be a minimum of
6” from the closest side wall.