Ldvt series direct vent gas fireplace, Below grade installations, Step 4 – Vermont Casting 43LDVT User Manual

Page 16: Step 5, Step 6, Step 7

Advertising
background image

16

LDVT Series Direct Vent Gas Fireplace

10007852

When it is not possible to meet the required vent ter-
minal clearances of 12” (305mm) above grade level a
snorkel vent kit is recommended. It allows installation
depth of down to 7” (178mm) below grade level. The 7”
is measured from the center of the horizontal vent pipe
as it penetrates through the wall.

If venting system is installed below
ground, we recommend a window well with
adequate and proper drainage.

Ensure sidewall venting clearances are observed.
If installing a snorkel a minimum 24” (610 mm) vertical
rise is necessary. The maximum horizontal run with
the 24” (610 mm) vertical pipe is 36” (914 mm). This
measurement is taken from the collar of the fireplace
(or transition elbow) to the face of the exterior wall.
Refer to the Sidewall Vent Graph for extended
horizontal run if the vertical rise exceeds 24” (610 mm).

1. Establish vent hole through the wall. (Fig. 18)
2. Remove soil to a depth of approximately 16” (406

mm) below base of snorkel. Install drain pipe. Install
window well (not supplied). Refill hole with 12” (305
mm) of coarse gravel leaving a clearance of approxi-
mately 4” (102 mm) below snorkel. (Fig. 26)

3. Install vent system.
4. Ensure a watertight seal is made around the vent

pipe coming through the wall.

5. Apply high temperature sealant caulking (supplied)

around the 4” and 7 “ snorkel collars.

6. Slide the snorkel into the vent pipes and secure to

the wall.

7. Level the soil to maintain a 4” (102 mm) clearance

below snorkel. (Fig. 26)

Below Grade Installations

Do not back fill around snorkel. A clearance
of at least 4” (102 mm) must be maintained
between snorkel and the soil.

If the foundation is recessed, use recess brackets (not
supplied) for securing lower portion of the snorkel.
Fasten brackets to wall first, then secure to snorkel
with self drilling #8 x 1/2 sheet metal screws. It will be
necessary to extend vent pipes out as far as protruding
wall face. (Fig. 27)

BG402a

Top Vent

Below grade installation

1/26/00 djt

Firestop

7” Pipe

7TDVSNORK

(Snorkel)

4” (102mm)

Clearance

Min.

Window

Well

Gravel

Drain

BG402

Fig. 26 Below grade installation.

Zero Clearance

Sleeve

(if required)

*A minimum of 24” (610mm) ver-

tical pipe must be installed when

using the 7TDVSNORK Kit.
*The 22” (559mm) vertical rise

(center to center) of the snorkel

may be included for calculationof

max. horizontal run.

24” (610mm)

Minimum*

Screws

Foundation Wall

Step 4

Install the 4” (102 mm) flex vent pipe to the appliance
collar as described on Page 11. Secure the end with the
first spring 6³⁄₄” (172 mm) from the flex pipe end to the
unit.

Step 5

Slide the 7” (178 mm) flex vent pipe over the 4” flex
vent pipe and secure the 7” collar as described on Page
11.

Step 6

Bend the flex pipe horizontal so the bottom of the
horizontal pipe measure 6¹⁄₂” (165mm) from the top of
the unit immediately after the 90° formation. (Fig. 25)
Be sure to follow the 1” (25mm) rise in a 24” (610mm)
horizontal run rule.

Step 7

Install the 4” flex then 7” flex to the termination.

6���" (165mm)

FP1475

flex 90 bend

4/04 djt

FP1475

Fig. 25 Bend flex vent at 90° so horizontal portion is 6¹⁄₂”
(165 mm) off top of unit.