Switches 1 to 5 select the device address. Switch 6 and 7 select the communication baud rate. Switch 8
enables encrypted communication. All other configuration settings are set via host software.

S8

S7

S6

S5

S4

S3

S2

S1

SELECTION

OFF

OFF

OFF

OFF

OFF

Address 0

OFF

OFF

OFF

OFF

ON

Address 1

OFF

OFF

OFF

ON

OFF

Address 2

OFF

OFF

OFF

ON

ON

Address 3

OFF

OFF

ON

OFF

OFF

Address 4

OFF

OFF

ON

OFF

ON

Address 5

OFF

OFF

ON

ON

OFF

Address 6

OFF

OFF

ON

ON

ON

Address 7

OFF

ON

OFF

OFF

OFF

Address 8

OFF

ON

OFF

OFF

ON

Address 9

OFF

ON

OFF

ON

OFF

Address 10

OFF

ON

OFF

ON

ON

Address 11

OFF

ON

ON

OFF

OFF

Address 12

OFF

ON

ON

OFF

ON

Address 13

OFF

ON

ON

ON

OFF

Address 14

OFF

ON

ON

ON

ON

Address 15

ON

OFF

OFF

OFF

OFF

Address 16

ON

OFF

OFF

OFF

ON

Address 17

ON

OFF

OFF

ON

OFF

Address 18

ON

OFF

OFF

ON

ON

Address 19

ON

OFF

ON

OFF

OFF

Address 20

ON

OFF

ON

OFF

ON

Address 21

ON

OFF

ON

ON

OFF

Address 22

ON

OFF

ON

ON

ON

Address 23

ON

ON

OFF

OFF

OFF

Address 24

ON

ON

OFF

OFF

ON

Address 25

ON

ON

OFF

ON

OFF

Address 26

ON

ON

OFF

ON

ON

Address 27

ON

ON

ON

OFF

OFF

Address 28

ON

ON

ON

OFF

ON

Address 29

ON

ON

ON

ON

OFF

Address 30

ON

ON

ON

ON

ON

Address 31

OFF

OFF

115,200 BPS, See note 1 below.

OFF

ON

9,600 BPS

ON

OFF

19,200 BPS

ON

ON

38,400 BPS

OFF

Encrypted communication not required

See note 2 below.

ON

Encrypted communication required

See note 2 below.

Note 1: Firmware revisions prior to 1.38.1, this setting is 2,400 BPS.

Note 2: Firmware revisions prior to 1.38.1, SW8 is not defined. Set to the OFF position.