LC-502W/LC-508W

5.4

Wiring Multiple Panels Together

Up to 32 floors can be controlled using LC-508Ws.

5.4.1

LC-508W/LC-502W Combination

Perform the following wiring instructions to accommodate an elevator application using an LC-
508W and one or more LC-502W panels.

1. Make a complete set of connections to the LC-508W panel. Refer to Section 5.3 on page 16 for

all connections to the LC-508W.

2. Daisy-chain the Wiegand Data0, Ground, and Data1 reader connections from W-TB-B to the

LC-502W panels. Make the connections per the information in Table 7 and Figure 12 on
page 19.

3. Daisy-chain the RS-485 TxRx+, TxRx-, and Shield network communication connections from

the W-TB-B terminal strip on the LC-508W to each of the LC-502W panels. Make the
connections per the information in Table 8 and Figure 13 on page 20.

4. Refer to Section 5.2.4 on page 16 for the LC-502W panel power connections.
5. Refer to Section 5.2.1 on page 10 for the LC-502W floor relay connections.

Table 7: LC-508W W-TB-B to LC-502W Panel

W-TB-B

Connection

LC-502W TB-5/TB-6

Pin 1

Reader Common

Pin 4

Pin 2

Data0

Pin 1

Pin 3

Data1

Pin 7

Table 8: LC-508W to LC-502W Panel

RS-485 Network Communication Wiring

W-TB-B

Connection

LC-502W TB-1

Pin 4

TxRx-

Pin 1

Pin 5

TxRx+

Pin 2

Pin 6

Shield

Pin 3