LAARS IGE-199C-5(N,X) - Service Manual User Manual
Page 11
Advertising
II - SPECIFICATIONS
(cont.)
COMBUSTION SPECIFICATIONS
Item
Gas Type
Natural
Propane
Gas Consumption
Minimum Btu's
15,000
15,000
Maximum Btu's
199,000
199,000
Injector Diameter
Upper
ø.045 (1.15mm)
ø.029 (.75mm)
Inches (mm)
Lower
ø.070 (1.8mm)
ø.045 (1.15mm)
Main Burner
B3A7-1 (Lean and Rich Bunsen Burner)
Main Damper
H73-115 (Upper: ø6, Lower: Not Used)
Gas Pressure
Supply/Manifold
Minimum Supply
6" W.C.
10" W.C.
Maximum Supply
10.5" W.C.
13.5" W.C.
Low Fire Manifold
0.56" W.C.
0.88" W.C.
High Fire Manifold
3.4" W.C.
5.1" W.C.