Anti-frost heaters do not operate

1) Are the ceramic anti-frost heaters operating normally?

2) Is the frost sensor switch operating normally?

a.

# Disconnect connector F4, and measure the

resistance of the heater mounted in the water

flow control valve, these are white wires.

Disconnect connector F5, and measure the

resistance of the heater in the outlet line

connector. See connectors in the first and second

picture to the left.

Normal: 348 ~ 375 Ω
If normal, proceed to b.
Faulty: Replace defective element.

b.

# Take an ohm meter and read resistance across

the heater on the face of the heat exchanger. The

resistance across this element is listed below. See

third picture to the left for location of this element.

These are white wires.

Normal: 100 ~ 110 Ω
If normal, proceed to check item 2 below.
Faulty: Replace defective anti frost heater

assembly.

c.

Check resistance of the two heat exchanger

outlet line heater elements, as shown in the

third picture to the left. Check across each heater

independently.

Normal: 33 ~ 39 Ω
Faulty: Replace defective anti frost heater
assembly.

a.

# Disconnect connector F2, and measure the

resistance through this switch, measure when

atmospheric temperature is 39°F + or – 3°F. (See Note)

See drawing to left for location of this bimetal

switch. These are white wires to this switch.

Normal: Less than 1 Ω

If normal, check wiring harness for defects.

(100 volts AC)

Faulty: Replace the frost sensing bimetal switch.

Note: If the atmospheric temperature is too high,

cool the switch with ice.

BEFORE CARRYING OUT CHECKS MARKED WITH A # SIGN, DISCONNECT THE POWER SUPPLY.