Mighty Venter Power Vent System

Page 5

1.

Locate the Vent Hood a minimum of 7 feet
(2.1m) above a public walkway.

2.

Locate the Vent Hood a minimum of 3 feet
(0.9m) above, or 4 feet (1.2m) below and 4 feet
(1.2m) horizontally from any door, window, or
gravity air inlet into the building. The Vent Hood
cannot terminate less than 6 feet (1.8m) above
any forced air inlet located within 10 feet (3.0m).

3.

The Vent Hood must be installed at least 3 feet
(0.9m) from any other building opening or any
gas service regulator.

4.

Do not install the vent hood closer than 2 feet
(0.6m) from an adjacent building.

5.

Install the Vent Hood no closer than 3 feet (0.9m)
from an inside corner of an L-shaped structure.

6.

Do not terminate the Vent Hood directly above a
gas utility meter or service regulator.

CODE REQUIREMENTS

The Power Venter installation must be in

accordance with the following requirements of the
National Fuel Gas Code:

All portions of the vent system under positive

pressure during operation (on the outlet side of the
Power Venter) shall be designed and installed so as to
prevent leakage of flue or vent gases into a building.

The boiler must enter the vent system on the inlet

side of the Power Venter.

Provision shall be made to interlock the

boiler(s) to prevent the flow of gas to the main burners
when the draft system is not performing so as to
satisfy the operating requirements of the equipment for
safe performance. See the “Electrical Wiring” section
in this manual for details.

Power Venter Installation

The Power Venter must be mounted with the

motor shaft horizontal to ensure proper operation of
the Fan-Prover switch and prevent motor bearing
wear (see Fig. 1). The installer must supply plumber's
strap or threaded rod with nut and washers for
mounting.

Figure 2. Side Wall Vent Hood Locations.

Vent Hood

7 (2.1) Minimum

Above Public

Walkway

Vent Hood

Vent Hood

1 (0.3) Above Grade

4 (1.2)

Minimum

4 (1.2)

Minimum

Vent Hood Must Be

Mounted At Least

4 (1.2) Below Windows

3 (0.9) Minimum

Vent Hood

4 (1.2)

Minimum

**

Vent Hood Must Be

Mounted At Least

3 (0.9) Above Windows

and Doors

Dimensions shown in feet (m).

6 (1.8) Above Any
Outside Air Intake

Within 10 (3.0)