LAARS Heating Systems

3a. Safety Interlock Test

1.

Turn the appliance thermostat/aquastat high
enough to call for heat.

2.

Verify by fan rotation that the Power Venter
begins operating before the gas valve becomes
energized.

3.

With the appliance firing and the Power Venter
operating, disrupt power to the Power Venter by
removing one of the black wires from the Power
Venter relay. Make sure the appliance gas valve
turns off.

WARNING

Do not operate the boiler that does not shut off when
the Power Venter is disabled.

3b. Maintenance

1.

Oil the motor every six months with 2 drops of
S.A.E. #20 oil. The oil ports are located on top of
the motor.

2.

Laars recommends that the boiler system be
checked annually by a qualified service
technician. The inspection should include
checking all vent pipe and connections for
blockage and leaks, and a safety interlock test.

Parts List

Part Number

Description

Boiler Size

10718702

Mighty Venter Kit (MV1)

175

D2008801

Power Venter

D0019700

Vent Hood, 7.6" Dia.

D0018800

4" x 6" Reducer (Qty. 1)

10718703

Mighty Venter Kit (MV1)

250

D2008801

Power Venter

D0019800

Vent Hood, 8.6" Dia.

D0018900

6" x 7" Reducer (Qty. 1)

D0018800

4" x 6" Reducer (Qty. 2)

10718704

Mighty Venter Kit (MV2)

325

D2008802

Power Venter

D0019800

Vent Hood, 8.6" Dia.

D0019000

6" x 8" Reducer (Qty. 1)

10718705

Mighty Venter Kit (MV2)

400

D2008802

Power Venter

D0019800

Vent Hood, 8.6" Dia.

D0019100

6" x 9" Reducer (Qty. 1)