Table 4.

NOTES:
1. The asterisk (*) denotes parts that are

included with the Mighty Venter kit.

2. To calculate the equivalent vent pipe

length, add the straight pipe plus 10 feet
(3.0m) for every 90° elbow and 5 feet
(1.5m) for every 45° elbow.

3. In order to use 100-foot (30.5m)

equivalent length of vent pipe with the
model 1670 boiler, consult factory. A
14 inch (356mm) vent pipe may be used.

4. To be used for single boiler installation

only.

5. Note that the Mighty Venter diameters

shown are for both the inlet and the
outlet of the Mighty Venter.

6. The vent pipe reducer kit includes item

D. And one of: Item E, Item G, Item H.
(As shown: varies per model.)

7. Reference Item “L” is used only with the

500 boiler. It is included with the
20069301 Mighty Venter kit.

8. The vent system must be adequately

supported to prevent sagging. But in no
case shall the supports be less than
every three feet (0.9m).

9. The venting system must be sloped

upward not less than ¼ inch per foot
from the furnace to the vent terminal. The
vent system must be installed to prevent
collection of condensate.

10. Side wall vent hood location: Read all

installation/operation information
concerning vent hood location before
installing.

E*

D*

C

A

18" (457mm) minimum
recommended rise
before elbowing to
horizontal run.

K

Equivalent Pipe Length
Calculate as per Notes 2
and 3 below.
Minimum equivalent vent
pipe length is 11' (3.4m)

(Slope: Note 9)

(Supports: Note 8)

Vent pipe is customer supplied

G*

H*

F

J

*

B

Reducer dimensions
For all sizes
(#1, #2, #3, #4)

B*

J

(Note 7)

Clearances to
combustibles:
6" (152mm) sides
8" (203mm) rear

L*

M*

P

N

(Note 10)

Side View

Figure 2. Part identification.

A

NOTE 1

B

C

NOTE 6

D

E

F

G

H

J

K

L, M

N

P

*

*

*

Boiler

Model

Size

Mighty

Venter Kit
Order No.

Power

Venter

Model

Ref.

Boiler

Vent

Outlet

In. (mm)

Vent Pipe

Reducer Kit

Part No.

Reducer Sizes Included In Reducer Kit

Mighty
Venter

Outlet

& Inlet

In. (mm)

Equivalent

Pipe

Length

(Max)
ft. (m)

Vent

Hood

P/N

Vent

Hood

Dia.

in. (mm)

Rough-In

Dimension

In. (mm)

Size

#1

Size

#2

Ref. Vent

Pipe Dia.

In. (mm)

Size

#3

Size

#4

500

20069301

MV-2

10 (254)

20070901

10-8

--

8 (203)

8-6

--

6 (152)

100 (30.5)

D2000401

8.50 (216)

9.0 (229)

600

20069302

MV-3

12 (305)

20070902 12-18

10-8

8 (203)

--

--

8 (203)

100 (30.5)

D2000402

10.12 (257) 10.62 (270)

715

20069303

MV-3

12 (305)

20070902 12-18

--

10 (254)

10-8

--

8 (203)

100 (30.5)

D2000402

10.12 (257) 10.62 (270)

850

20069304

MV-4

14 (356)

20070903 14-10

--

10 (254)

10-8

--

8 (203)

100 (30.5)

D2000402

10.12 (257) 10.62 (270)

1010 20069305

MV4

16 (406)

20070904 15-14

14-12

12 (254)

12-10

10-8

8 (203)

100 (30.5)

D2000402

10.12 (257) 10.62 (270)

1200 20069306

MV-5

16 (406)

20070905 15-14

14-10

10 (254)

--

--

10 (254)

100 (30.5)

D2000403

13.25 (337) 13.75 (349)

1430 20069307

MV-5

18 (457)

20070906 18-14

14-10

10 (254)

--

--

10 (254)

100 (30.5)

D2000403

13.25 (337) 13.75 (349)

1670 20069308

MV-5

18 (457)

20078907 18-14

14-12

12 (305)

12-10

--

10 (254)

80 (24.4)

D2000403

13.25 (337) 13.75 (349)

1825 20069309

MV-5

18 (457)

20070906 18-14

--

14 (356)

14-10

--

10 (254)

100 (30.5)

D2000403

13.25 (337) 13.75 (349)