2C. Adjustments

Set the differential to correspond with the boiler

manufacturer recommendations. To adjust models

with adjustable differential, rotate the wheel on the

back of the snap switch until the desired reading is

aligned with the V notch in the frame. The wheel

provides an adjustment from 5 to 30 degrees (F).

Replace the cover on the aquastat controller.

Adjust the control point to correspond with the

boiler manufacturer's recommendations. To adjust,

insert a screwdriver in the slotted screw-type head

located beneath the window in the cover. Turn the

scale to the desired control point.

2D. Checkout

Check to make certain the aquastat controller is

installed and adjusted properly. Operate the system

and observe the action of the device through several

cycles to make certain that it provides proper low limit

cut-out protection and circulator control. Make any

further adjustments needed.

Figure 7. Typical Connection Diagram for an Oil-Fired
Hydronic Heating System That Provides Year Around
Domestic Hot Water.