SECTION 1.
General Information

WARNING

This manual supplies information on the application,
installation and operation of the indirect water heater
unit. A complete instruction manual of the operation of
the hydronic boiler (Document 1025) is supplied along
with this manual. Both manuals should be reviewed
completely before proceeding with the installation.
• Failure to follow the instructions provided may result

in personal injury, death or substantial property
damage.

• Any modifications to the boiler, water tank, gas and

water connections, or wiring may void warranty.

• Consult the factory or local factory representative

with any questions or problems regarding this
equipment.

AVERTISSEMENT

Ce manuel donne des renseignements sur
l’application, l’installation et le fonctionnement du
chauffe-eau indirect. Un manuel complet d’instruction
sur le fonctionnement de la chaudière hydronique
(Document 1025) est fourni avec ce manuel. Les deux
manuels doivent être examinés attentivement avant
de procéder à l’installation.
• Si les instructions ne sont pas suivies, il peut en

résulter des blessures personnelles, la mort ou des
dégâts matériels substantiels.

• Toute modification apportée à la chaudière, au

réservoir d’eau, aux branchements de gaz et d’eau
ou aux fils électriques peut invalider la garantie.

• Consultez le représentant de l’usine principale ou

locale pour toute question ou problème concernant
ce matériel.

1.1 Hazards and Your Safety

- Hot Water Can Scald!

The Consumer Product Safety Commission (CPSC)

and some states/provinces recommend a temperature

setting of 130°F (54°C) or less. The water heater

thermostat is factory set to approximately 120°F (49°C).

If thermostat will be set above factory setting, install an

anti-scald valve at either the water heater or at each hot

water faucet.

Tempering valves are not anti-scald valves since

they do not have a positive shutoff in case cold

water supply fails. They are not recommended for

shower/tub service. If needed, install an anti-scald

valve at each shower/tub.

Water heated to a temperature suitable for clothes

washing, dish washing and other sanitizing needs

can scald and cause permanent injury.

Children and elderly, infirmed, or physically

handicapped persons are more likely to be injured

by hot water. Never leave them unattended in a

bathtub or shower. Never allow small children to

use a hot water tap or draw their own bath. If

anyone using hot water in the building fits this

description, or if state/province laws or local codes

require certain water temperature at hot water taps,

take special precautions:
Install an anti-scald valve at water heater or at each

hot water faucet, bath, and shower outlet.
Use lowest practical temperature setting.

Studies have indicated that dangerous bacteria can

form in potable water distribution system if certain

minimum water temperatures are not maintained.

Contact local health department for more

information.

SECTION 2.
Installation

This installation must conform with the instructions

in this manual and, where applicable:

National Fuel Gas Code (ANSI Z223.1).

National Electric Code (NEC-NFPA 70).

Local, state, provincial, and national codes, laws,

regulations and ordinances.

In Canada - Natural Gas and Propane Installation

Code, CSA B149.1 and the Canadian Electric Code

(CEC - Can/CSA C22.1.

Where the recommendations made in this manual

differ from local or national codes, the local or national

codes take precedence.

2.1 Location

This water heater/boiler unit is not intended for

outdoor installation. Select a convenient location where

water leakage from the tank or connections will not result

in damage to areas adjacent to the appliance or to lower

floors of the structure. When a safe location cannot be

found, install a suitable drain pan under the appliance,

and pipe it to an adequate drain.

2.2 Heater Placement

The heater must be placed to provide clearances on

all sides for maintenance and inspection. Allow 4 inches

(102mm) on each side for piping access. There must also

be minimum distances maintained from combustible

surfaces. Figure 2 shows minimum clearance from

combustible surfaces. The Mini-Combo unit can be

installed in a closet, as long as the minimum clearances

are maintained. Special attention should be paid to the air

supply opening to the closet. Refer to Table 1.