6612_OMU_S2_URT_V1_13 Firmware Description Document

FDD_6612_010

44

Rev. 1.1

MPU

Parameter

Location

(hex)

LSB

Default

Comment

Example

Peak IB_wb

Alarm

Threshold

DF

mArms

+15.000

Maximum Wideband Current

measured on the IB channel

above which a flag must set

(bit 14 of the Alarm Status

Register).

If the peak wideband

current threshold on

Outlet 2 is to be changed

from the default value of

15 Amps to 30 Amps

then set as follows:

)DF=+30.000<CR>

PFB_nb_Neg

Threshold

E0

-0.700

Narrowband Power Factor

Negative Threshold for Outlet

2. A less negative narrowband

power factor than this

threshold will set an alarm (bit

15 of the Alarm Status

Register).

If the negative

narrowband power factor

threshold on Outlet 2 is
to be changed from the

default to -0.6 then set

as follows:

)E0=-0.600<CR>

PFB_nb_Pos

Threshold

E1

+0.700

Narrowband Power Factor

Positive Threshold for Outlet 2.

A narrowband power factor

less than this threshold will set

an alarm (bit 16 of the Alarm

Status Register).

If the positive

narrowband power factor

threshold on Outlet 2 is
to be changed from the

default to +0.600 then

set as follows:

)E1=+0.600<CR>

PFB_wb_Neg

Threshold

E2

-0.700

Wideband Power Factor

Negative Threshold for Outlet

2. A less negative wideband

power factor than this

threshold will set an alarm (bit

17 of the Alarm Status

Register).

If the negative wideband

power factor threshold

on Outlet 2 is to be

changed from the default

to -0.6 then set as

follows:

)E2=-0.600<CR>

PFB_wb_Pos

Threshold

E3

+0.700

Wideband Power Factor

Positive Threshold for Outlet 2.

A positive wideband power

factor less than this threshold
will set an alarm (bit 18 of the

Alarm Status Register).

If the positive wideband

power factor threshold

on Outlet 2 is to be

changed from the default

to +0.6 then set as

follows:

)E3=+0.600<CR>

Peak I

Total_nb

Alarm

Threshold

E4

mArms

+20.000

Maximum Narrowband Current

measured on Outlet 1 plus

Outlet 2 above which a flag

must be set (bit 19 of the

Alarm Status Register).

If the narrowband peak

current threshold on

Outlet 1 plus Outlet 2 is

to be changed from the

default value of 20 Amps

to 30 Amps then set as

follows:

)E4=+30.000<CR>