6612_OMU_S2_URT_V1_13 Firmware Description Document
FDD_6612_010
44
Rev. 1.1
MPU
Parameter
Location
(hex)
LSB
Default
Comment
Example
Peak IB_wb
Alarm
Threshold
DF
mArms
+15.000
Maximum Wideband Current
measured on the IB channel
above which a flag must set
(bit 14 of the Alarm Status
Register).
If the peak wideband
current threshold on
Outlet 2 is to be changed
from the default value of
15 Amps to 30 Amps
then set as follows:
)DF=+30.000<CR>
PFB_nb_Neg
Threshold
E0
–
-0.700
Narrowband Power Factor
Negative Threshold for Outlet
2. A less negative narrowband
power factor than this
threshold will set an alarm (bit
15 of the Alarm Status
Register).
If the negative
narrowband power factor
threshold on Outlet 2 is
to be changed from the
default to -0.6 then set
as follows:
)E0=-0.600<CR>
PFB_nb_Pos
Threshold
E1
–
+0.700
Narrowband Power Factor
Positive Threshold for Outlet 2.
A narrowband power factor
less than this threshold will set
an alarm (bit 16 of the Alarm
Status Register).
If the positive
narrowband power factor
threshold on Outlet 2 is
to be changed from the
default to +0.600 then
set as follows:
)E1=+0.600<CR>
PFB_wb_Neg
Threshold
E2
–
-0.700
Wideband Power Factor
Negative Threshold for Outlet
2. A less negative wideband
power factor than this
threshold will set an alarm (bit
17 of the Alarm Status
Register).
If the negative wideband
power factor threshold
on Outlet 2 is to be
changed from the default
to -0.6 then set as
follows:
)E2=-0.600<CR>
PFB_wb_Pos
Threshold
E3
–
+0.700
Wideband Power Factor
Positive Threshold for Outlet 2.
A positive wideband power
factor less than this threshold
will set an alarm (bit 18 of the
Alarm Status Register).
If the positive wideband
power factor threshold
on Outlet 2 is to be
changed from the default
to +0.6 then set as
follows:
)E3=+0.600<CR>
Peak I
Total_nb
Alarm
Threshold
E4
mArms
+20.000
Maximum Narrowband Current
measured on Outlet 1 plus
Outlet 2 above which a flag
must be set (bit 19 of the
Alarm Status Register).
If the narrowband peak
current threshold on
Outlet 1 plus Outlet 2 is
to be changed from the
default value of 20 Amps
to 30 Amps then set as
follows:
)E4=+30.000<CR>