Vertical through the roof applications – Vermont Casting D232 User Manual

Page 14

Advertising
background image

- 14 -

GRAVEL

DRAIN

FIRESTOP

FOUNDATION WALL

WINDOW WELL

SNORKEL

GROUND

24"/608mm

MINIMUM*

A minimum of 24"/608mm
vertical pipe must be installed
when using the snorkel kit.

The 22" vertical rise (center to
center) of the snorkel may be
included for calculation of max.
horizontal run.

*

7" PIPE

SCREWS

4" CLEARANCE

*

Fig. 22

1.

Establish vent hole through the wall (Fig. 13,14 & 15).

2.

Remove soil to a depth of approximately 16" below
base of snorkel. Install drain pipe. Install window well
(not supplied). Refill hole with 12" of coarse gravel
leaving a clearance of approximately 4" below snorkel.
See Fig. 22.

3.

Install vent system.

4.

Ensure a watertight seal is made around the vent pipe
coming through the wall.

5.

Apply high temperature sealant caulking (supplied)
around the 4 and 7 inch snorkel collars.

6.

Slide into vent pipe and secure to the wall.

7.

Level the soil so as to maintain a 4" clearance below
snorkel. See Fig. 22.

DO NOT BACK FILL AROUND SNORKEL.
SOIL SHOULD NOT BE LESS THAN 4"
BELOW SNORKEL.

FOUNDATION

RECESS

SNORKEL

SCREWS

WALL

SCREWS

SHEET METAL

WATERTIGHT

SEAL

AROUND

PIPE

If the foundation is recessed, use recess brackets (not
supplied) for securing lower portion of the snorkel. Fasten
brackets to wall first and then secure to snorkel with self drilling
#8 x 1/2 sheet metal screws. It will be necessary to extend the
vent pipes out as far as the protruding wall face (Fig. 22).

Fig. 23

VERTICAL THROUGH THE ROOF

APPLICATIONS

This Gas Fireplace has been approved for,
a) Vertical installations up to 40 feet (12 metres) in height.

Up to a 10 ft. horizontal vent run can be installed within
the vent system using a maximum of two 90

o

elbows.

(Fig. 24)

b) Up to two 45

o

elbows may be used within the horizontal

run. For each 45

o

elbow used on the horizontal level

the maximum horizontal length must be reduced by 18
inches.

Example: Maximum horizontal length

0

-

45

o

elbows

10 ft.

1

-

45

o

elbows

8.5 ft.

2

-

45

o

elbows

7 ft.

Ensure sidewall venting clearances are observed.

If installing a snorkel a minimum 24" vertical rise is
necessary. The maximum horizontal run with the 24"
vertical pipe is 36" (915mm). This measurement is
taken from the collar of the fireplace to the face of the
exterior wall. See vent graph for extended horizontal
run if the vertical exceeds 24".

Fig. 24

MAXIMUM

10 FT

(305cm)

PIPE STRAPS

EVERY 3’

(92cm)

MINIMUM

8 FT./

MAXIMUM

40 FT.

VERTICAL

RISE