Preparing for Operation

3-13

Positioner SIPART PS2/SIPART PS2 PA
C79000-G7476-C150–01

3.4.2 Connection variants not protected from explosion hazard (devices

with PROFIBUS PA)

!

Warning

The applicable regulations for electrical installation must be observed,
in particular, in zones subject to explosion hazard

❑

the regulation about electrical equipment in zones subject to explo-
sion hazard. The erection guidelines of the country in question must
be observed.

❑

the regulation about erection of electrical equipment in zones sub-
ject to explosion hazard (DIN VDE 0165)

❑

the certificate of conformity

❑

It is necessary to check whether the auxiliary power supplied by the
coupler matches the value specified on the rating plate of the SI-
PART PS2 PA and in the Ex certification.

If the intrinsically safe version is operated with an operating voltage of
more than 24 V by mistake, the device must no longer be used for in-
trinsically safe applications.

The positioner is powered via the PROFIBUS PA by the DP/PA coupler
or DP/PA link. The devices draw their electrical auxiliary power from a
power supply unit with SELV (safety extra–low voltage).

☞

Note

The following generally applies to laying the bus cable:

❑

Lay cables separated from cables carrying > 60 V

❑

Avoid the vicinity of large electrical equipment

❑

Only use recommended cable types

❑

The specifications only apply to properly installed equipment

Only use a shielded, two–conductor cable as the bus cable.
The recommended cable types are:
Ex i applications:

Siemens 6XV1 830–5AH01 (color blue)

Non Ex applications:

Siemens 6XV1 830–5BH10 (color black)

The mechanical and electrical data of these two cable types are identi-
cal.

1. Strip back the bus cable insulation as shown in Fig.3-11.

2. Open the housing of the positioner by loosening the four screws of

the cover.

Assembling the
bus cable