Technical data – Moniteur 50 Series SMART Positioners User Manual

Page 99

Advertising
background image

Technical Data

6-1

Positioner SIPART PS2/SIPART PS2 PA
C79000-G7476-C150–01

Technical Data

General data: basic instrument 6DR400x–xx (without PROFIBUS PA) and 6DR410x–xx
(with PROFIBUS PA)

Climatic category IEC 721

Storage

1K5 but – 40

°

C to + 80

°

C

1)

Transport

2K4 but – 40

°

C to + 80

°

C

1)

Operation without purging air

3K3 but – 30

°

C

3)

to + 80

°

C

2)

with purging air

3K4 but – 30

°

C

3)

to + 80

°

C

2)

Degree of protection

IP65 acc. to EN60529

Dimensions

plastic housing

see Fig. 3-2

metal housing

see Fig. 3-4

Weight

basic instrument

plastic

approx 0.9 kg

metal

approx. 1.3 kg

Resistance to vibration

5 g acc. to IEC 48–2–6 with NAMUR mount-
ing

8 g (10 g) acc. to IEC 48–2–6 with ARCA
mounting or “rotary actuator”

4)

Termination system

electrical signals

screw terminals 1.5 AWG14

cable gland PG 13

pneumatic signals

internal thread G 1/4 DIN 45141

Mounting position

any, outlet air opening and controller output
axis not upwards

Material

housing

plastic

fibre–glass reinforced polyester

metal

anodized Gk–Al Si 7Mg

pneumatic connection block
for plastic housing

anodized Al Mg Si < 6

CE symbol

conforms to EMC directive 89/336 EEC in
accordance with the following standards

Emitted interference

EN 50 081–1

Immunity to interference

EN 50 082–2 and NAMUR NE21 May 93

1)

When commissioning at

v

0

°

C, ensure the valves are purged with the dry medium for a sufficiently long period

2)

See technical data for basic instrument and option for ex-proof instruments

3)

Reduced refresh rate of the LCD display below –10

°

C

4)

To 100 Hz

6

Advertising