Table 2 — Physical Data

19EA Pumpout Unit

ENGLISH

(SI)

Pumpout Unit Weight*

lb (kg)

210

(95)

Pumpout Condenser Water Flow Rate

gpm (L/s)

5 to 7

(.32 to .44)

Pumpout Condenser Water Pressure Drop

psig (kPa)

6 to 10.7

(41.4 to 73.8)

Maximum Entering Condenser Water Temperature

F (C)

85

(29)

Maximum Leaving Condenser Water Temperature

F (C)

100

(37)

Condenser Relief Valve (Fusible Plug)

psig (kPa)

385

(2655)

Condenser Pressure Rating

Refrigerant Side

psig (kPa)

385

(2655)

Waterside

psig (kPa)

150

(1034)

Compressor Rating 1750 rpm (29 r/s) Reciprocating

cfm (L/s)

8.7

(.25)

Valves (4-Valve Manifold, Copper with

Brass Turn Knob Valves)

in. OD

1

2

1

2

*The pumpout unit weight includes the compressor/condenser, control box, and the oil separator.

NOTES:
1. The motor is hermetic with thermal protection.
2. The control box is mounted and wired with a fuse on/off switch according to NEMA 1 (National

Electrical Manufacturing Association).

3. The starter contactor is located in the control box. The overloads on the motor are wired and the

disconnect switch is supplied by the customer.

4. The condenser tube is copper.

Fig. 4 — Rigging Guide

STORAGE

TANK SIZE

CENTER OF GRAVITY

APPROX. DIM. — ft-in. (mm)

EMPTY WEIGHT

LB (Kg)

A

B

28 Ft

3

4- 5

1

4

(1353)

1-7

7

8

(505)

2380

(1080)

52 Ft

3

6-10

1

8

(2086)

1-8

3

4

(527)

3460

(1569)

NOTES:
1. Each chain must be capable of supporting the entire weight of the

machine.

2. Minimum chain length:

28 ft

3

tank — 10

Ј

-0

Љ

52 ft

3

tank — 15

Ј

-6

Љ

3. Total weight equals empty weight from chart and charge weight

given on label.

6