Carrier POSITIVE PRESSURE STORAGE SYSTEM 19XB User Manual

Page 9

Advertising
background image

GENERAL PIPING CONNECTION SIZES

CONNECTION

SIZE (in.)

Refrigerant Transfer Connections

1

2

ODS (female)

Condenser Water Cooling Connectors

1

2

NPT (female)

Safety Relief Head Pumpdown Condenser

3

8

Flare (male)

ODS — Outside Diameter, Sweat

LEGEND

Factory-Supplied Tubing

Field-Supplied Tubing

Field-Supplied Tubing (Multiple Chillers)

Service Valve (Factory Supplied)

Service Valve (Field Supplied)

NOTES:
1. The field-supplied tubing is to be

1

2

-in. OD tubing (min.) and must

be arranged and supported to avoid stresses on the equipment,
transmission of vibrations, and interference with routine access
during the reading, adjusting, and servicing of the equipment. If
the distance from the chiller to the pumpout unit is over 50 ft, then

7

8

-in. OD tubing (min.) must be used. Provisions should be made

for adjustment in each plane of the tubing and for both periodic
and major servicing of the equipment. Special care must be taken
so that the safety head does not experience tubing strain. Vent
the safety head per ASHRAE 15 (American Society of Heating,
Refrigeration, and Air Conditioning Engineers), latest revision.

2. The tubing and valve from the storage tank to the pumpout com-

pressor is factory supplied when the unit is factory mounted.

Fig. 6 — Typical Pumpout Unit/Chiller Connection Schematic

CHILLERS WITHOUT ISOLATION VALVES

CHILLERS WITH ISOLATION VALVES

(WITH OR WITHOUT PUMPOUT STORAGE TANKS)

9