Potter PFC-5000 Series User Manual

Page 22

Advertising
background image

18

Polarity Reversal and City Tie Module (Model:PR-5100) Terminal Connections

See Appendix C on page 37 for module specifi cations. Wire as shown in Figure 15 below using proper wire gauges. Refer to
LT-877POT for more details.
Note that for use in the USA, the installer must add an Atlantic Scientifi c (Tel. 407-725-8000) Model #24544 Protective Device,
or similar ULI-Listed QVRG Secondary Protector, as shown. For use in Canada, the protective device is still recommended, but
the PR-5100 may be connected directly to polarity reversal and city tie wiring.

If UDACT-9100 and PR-5100 are used then

Protector not needed. UDACT-9100 has integral protector and PR-5100 is plugged into it.

Notes:

The terminal blocks are “depluggable” for ease of wiring.

•

The city tie interface is

•

not power limited.

Use either the PR-5100’s City Tie or Reverse Polarity Interface Module - not both.

•

Figure 15: PR-5100 Polarity Reversal and City Tie Module Terminal Connections

When wiring devices, please keep in mind the following:

Plug PR-5100 ribbon cable (P1) into the main fi re alarm module.

•

All circuits are power limited and must use type FPL, FPLR, or FPLP power limited cable.

•

For polarity reversal operation, short the city tie connection.

•

+

-

USE A SHORTING WIRE WHEN

THE CITY TIE IS NOT IN USE.

PROTECTED

+

-

2

1

S

1

2

S

1

1

2

2

S

S

POLARITY REVERSAL ALARM

24VDC OPEN

12VDC AT 3.5 mA

8 mA MAX SHORT

PR-5100

UNPROTECTED

+

+

-

-

DIN RAIL CONNECTION

TO EARTH GROUND

CITY TIE LOCAL ENERGY

RATED 24 VDC FILTERED

TRIP COIL 14 OHMS,

250mA, 5mV RIPPLE

CONFORMS TO NEMA STANDARD

SB3-1969 INTENDED FOR

CONNECTION TO POLARITY

REVERSAL CIRCUIT OF A REMOTE

STATION RECEIVING UNIT HAVING

COMPATIBLE RATINGS.

PROTECTOR

1

2

S

1

2

S

UNPROTECTED

PROTECTOR

PROTECTED

2

1

S

1

2

S

+

-

DIN RAIL CONNECTION

TO EARTH GROUND

POWER LIMITED

POWER LIMITED

+

POLARITY REVERSAL SUPV

24VDC OPEN

12VDC AT 3.5 mA

8 mA MAX SHORT

POWER LIMITED CABLE TYPE FPL,

FPLR OR FPLP MUST BE USED FROM

PR-5100 TO PROTECTORS