25

Operation

All alarm inputs are treated in a similar manner. Alarm inputs include non-verifi ed or verifi ed alarms, and water-fl ow alarms.
Activation of any alarm input when the panel is not already in alarm cause the following:

The buzzer sounds steadily

•

If fi re drill is active, it is cancelled

•

The Common Alarm indicator turns on

•

The common alarm relay activates if aux disconnect is not active

•

The Auto Signal Silence timer, if confi gured, starts

•

The Signal Silence Inhibit timer, if confi gured, starts

•

ARM-4 / ARM-8 relays are activated as confi gured, provided that aux disconnect is not active

•

Signals and strobes are activated

•

Subsequent Alarms when the panel is already in alarm, cause the following:

The buzzer sounds steadily

•

If signals have been silenced as a result of the signal silence button or the auto signal silence timer, signals are resounded as

•

they were before signal silence, the signal silence indicator is turned off, and the auto signal silence timer, if confi gured, is
restarted
Signals and strobes are activated

•

Circuit Types

The term circuits refers to an actual electrical interface, either initiating (detection) or NAC (signal). The term zone is a logical
concept for a fi re alarm protected area, and will consist of at least one circuit. Often the terms zone and circuit are used
interchangeably, but in this manual the term circuit is used.