5-92

PFC-6075 • 5403593 • Rev C • 2/13

Fire Communications Bridge (FCB-1000)

The panel supports one (1) FCB-1000. The FCB-1000 provides a remotely-located IP connection into the panel, which may be

designated as the IP reporting device versus passing through the on-board internet connection.

To add and configure the FCB-1000 bridge:

Select

1.

FCB-1000 from the system panel.

Click the

2.

Add Device button. The “Add Device” window displays.

Example of Add FCB-1000 Window

Figure 129.

Double-click in the

3.

“Name” field to customize name.

Double-click in “

4.

Address” field to adjust address, if needed.

Click the

5.

plus sign located in the left-most column to display the "Network Settings" options.

Example of Add FCB-1000 Window

Figure 130.

Set the IP address by choosing one of the following two methods:

6.

The built in DHCP (Dynamic Host Configuration Protocol) option is the default; an IP address is automatically requested

•

from the “Host Computer".

The Network Administrator or Installer may set the IP address using the software's

•

Static IP function.

Click the

7.

minus sign located in the left-most column to suppress the "Network Settings" options from the window.