The PFC-7500 Series panels can provide two programmable auxiliary Form C (SPDT) relays when equipped with plug-

in relays in sockets OUTPUT 1 and OUTPUT 2. Each relay is rated for 1 Amp at

30 VDC (allows .35 power factor).
Each output provides one Common, one Normally Open, and one Normally Closed terminal. Field wiring for the Form C

relays connects to the 6-position terminal strip on the lower right corner of the PFC-7500 Series boards.
The Form C relays can be operated by any of the functions listed below:

1) Activation by a zone condition

3) Fire alarm or Fire trouble

2) Communication Failure

Annunciator Outputs

13.1

Description

The PFC-7500 Series panels provide four programmable open collector annunciator outputs that can be programmed to

indicate the activity of the panel zones or conditions occurring on the system. Open collector outputs do not provide a voltage

but instead switch to ground voltage from another source. Each annunciator output is rated for 50mA at 30 VDC resistive.
Form C and Annunciator outputs operate together: The Form C outputs 1 and 2 are internally connected to the

Annunciator outputs 1 and 2. Any options assigned to Output 1 or 2 in the panel’s Output Options programming applies

to both outputs. While the Form C outputs each require a Plug-in Relay, the annunciator outputs work without the relays.
The Annunciator outputs can respond to any of the conditions listed below:

1) Activation by zone condition

2) Communication failure

3) Fire Alarm, Fire Trouble, or Supervisory

13.2

Harness Wiring

The Annunciator outputs are accessible by installing the Harness on the 4-pin header labeled J12. The output locations

are shown below:

Output

Color

Wire

1

Red

1

2

Yellow

2

3

Green

3

4

Black

4

Devices connected to the outputs must be located within the same room as the PFC-7500 Series panels.

Telephone RJ Connector

14.1

Description

Connect the panel to the public telephone network by installing RJ Cables between the panel’s J4 (MAIN) and J5

(BACKUP) connectors, and the RJ31X or RJ38X phone jacks on the 356 cable. The maximum line impedance is 100 Ohms.

14.2

FCC Registration

The PFC-7500 Series panels comply with FCC part 68 and are registered with the FCC.
Registration number: CCKUSA - 1SNM0 - AL - R
Ringer Equivalence: 1.1B