Power supply, Sm-12/24 module – Potter PFC-7500 Series User Manual

Page 22

Advertising
background image


18

22.3

SNM Class B Style W using Multiple Notification Appliances

1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble

Normal/Silence Switch

Potter Model SNM

45mA @ 12 VDC

The SNM Notification

Appliance Circuit

Module in alarm draws

up to 31mA through

its Terminal 3 Alarm

Input and 45mA from

its Terminal 1 Aux

Power Input.

Panel Reset

AC

1

2

3

4

7

8

10 11 12 13

14 15 16

AC

B+

B-

9

RED

YEL

GRN BLK

Z1B-

Z2 -

Z2+

1

2

3

4

J12

Z1A- Z1B +

Z1A +

PFC-7500 SeriesCommercial Fire Command

Processor Panel

MAIN

BACKUP

J11

N/C COM N/O N/C COM N/

O

Telephone Connections

J10 Trouble Annunciator Header

5

6

BELL

SM K

O

U

TP

U

T

1

O

U

TP

U

T

2

SILENCE/RESET

PUSH FOR ONE SECOND

S ilence/Reset

B utton

S ilence/Reset

Header

17 18

Z3 -

Z3+

19 20

Z4 -

Z4+

21 22

Z5 -

Z5+

Bell

Monitor

r

J13

J14

Power Supply

J6

+ DC -

AC

Trouble

Batt

Trouble

J4

J3

J2

Green

LED

AC

AC

+ BAT -

Red

LED

DC

12 VDC @ 5 Amps

Battery

Start

TAM Module

Auxiliary Power Supply must be regulated, power

limited, and listed for Fire Protective Signaling

Service. Power Supplies must have battery backup.
Note: If an auxiliary power supply is not used,

terminals 3 and 4 can be jumpered together to

supply Bell Power from the panel.

The Auxiliary Power Supply and Notification

Circuit Module trouble contact zone must be

programmed as a Supervisory Type zone.

SM-12/24 Module

Polarized Notification

Appliances

10K EOLR

Sync module

required when using

multiple notification

appliances

See the Notification Appliance

section for a list of appliances.

The maximum voltage drop

between the panel Bell Output and

the EOLR is .5 VDC when a separate

power supply is not used.

When using a separate power supply, the

maximum current is 3 Amps.

The Bell Output

programming for Fire

type zones must be set

to Steady.

Regulated

12 VDC

Advertising