Hardwire 2-Wire Smoke Detector Compatability (United States):

1) The below listed Smoke Detectors are compatible with Initiating Circuits having Compatibility Identifier “A”.

Smoke Detector Make/Model Base Compatibility Identifier Head/Base

Rated Standby Current

POTTER

IS-24/SB-93

HD-3/HB-3

0.040mA

PS-24/SB-93

HD-3/HB-3

0.045mA

PS-24H/SB-93

HD-3/HB-3

0.045mA

BPS-2/NA

HD-6

55uA@24 VDC

HOCHIKI

DCD-190/HSC-220R

HD-3/HB-72

0.035mA

DCD-190/NS6-220

HD-3/HB-3

0.035mA

DCD-190/NS4-220

HD-3/HB-3

0.035mA

DCD-135/HSC-220R

HD-3/HB-3

0.035mA

DCD-135/NS6-220

HD-3/HB-3

0.035mA

DCD-135/NS4-220

HD-3/HB-3

0.035mA

SIJ-24/HSC-220R

HD-3/HB-72

0.040mA

SIJ-24/NS6-220

HD-3/HB-3

0.040mA

SIJ-24/NS4-220

HD-3/HB-3

0.040mA

SLR-24/HSC-220R

HD-3/HB-72

0.045mA

SLR-24/NS6-220

HD-3/HB-3

0.045mA

SLR-24/NS4-220

HD-3/HB-3

0.045mA

SLR-24H/NS6-220

HD-3/HB-3

0.045mA

SLR-24H/NS4-220

HD-3/HB-3

0.045mA

SLR-24H-HSC-220R

HD-3/HB-72

0.045mA

SLR-835/NS6-220

HD-3/HB-3

0.045mA

SLR-835/NS4-220

HD-3/HB-3

0.045mA

SLR-835/HSC-220R

HD-3/HB-72

0.045mA

SLR-835B-2

HD-6

55uA@24 VDC

SENTROL - ESL

429C

S10A-N/A

0.10mA

429CT

S10A-N/A

0.10mA

429CST

S11A-N/A

0.10mA

429CRT

S11A-N/A

0.10mA

711U/701E, 701U, 702E, 702U

S10A-S00

0.10mA

712U/701E, 701U, 702E, 702U

S10A-S00

0.10mA

7135U/701E, 701U, 702E, 702U

S10A-S00

0.10mA

7136U/701E, 701U, 702E, 702U

S10A-S00

0.10mA

721U/702E, 702U

S10A-S00

0.10mA

721U/702E, 702U

S10A-S00

0.10mA

722U, 702E, 702U

S10A-S00

0.10mA

731U/702E, 702U, 702RE, 702RU

S11A-S00

0.10mA

732U/702E, 702U, 702RE, 702RU

S11A-S00

0.10mA

Do not mix different brands of smoke detectors on the same initiating circuit.