Potter EVD-2 User Manual

Page 17

Advertising
background image

17

EVD-2 • 5401042 • REV N • 6/09

Figure 11 Dimensions

All dimensions in inches

Figure 12 EVD-M or EVD-R Mounting Template

Table 8 Recommended Maximum EVD-M/EVD-R Spacing for Wall Protection

Material

Sensitivity
Setting

Detector
Range

Rectangular Area of 100% Coverage

Steel plate at least
1/4" thick

Minimum

8.0'

11.3' x 11.3'

8' x 13.9'

10' x 12.5'

15' x 5.6'

-

Half

15.0'

21.2' x 21.2'

8' x 28.9'

10' x 28.3'

15' x 26'

20' x 22.4'

Maximum

20.0'

28.3' x 28.3'

8' x 39.2'

10' x 38.7'

15' x 37.1'

20' x 34.6'

Monolithic concrete
at least 6" thick

Minimum

16.0'

22.6' x 22.6'

8' x 31.0'

10' x 30.4'

15' x 28.3'

20' x 25.0'

Concrete block at
least 6" thick

Minimum

16.0'

22.6' x 22.6'

8' x 31.0'

10' x 30.4'

15' x 28.3''

20' x 25.0'

All dimensions in inches

Advertising