Reznor RXH (Outdoor PreevA) Unit Installation Manual User Manual

Page 17

Advertising
background image

Form I-RDH/REH/RHH/RXH (12-14), P/N 215210 R14, Page 17

1) Gas Valve Pressure Tap Locations
Locate the 1/8” outlet pressure tap on the single or two-stage valve (See

FIGURE

11A). With the manual valve turned off to prevent flow to the gas valve, connect a

manometer to the 1/8” outlet pressure tap in the valve. Both high-fire and low-fire outlet

pressure can be checked at this pressure tap.

2) Measure Outlet Pressure and Adjust (if needed)
Open the manual valve and operate the heater.
Using the manometer connected to the valve, measure the outlet pressure of the sin-

gle-stage gas valve or high fire on a two-stage valve. To measure low-stage pressure

on units with a two-stage valve (Options AG2, AG3, AG15, AG16, AG60, AG61, AG62,

DG1, DG5, and D12C), disconnect the wire from the “HI” terminal on the valve. Mea-

sure gas pressure with the manometer attached to the valve. Re-connect the wire.
Normally, when operating at the altitude indicated on the rating plate, adjust-

ments to the factory settings should not be necessary. If adjustment is required,

remove the cap from the adjustment screw on the single or two-stage valve. Adjust

pressure setting by turning the regulator screw IN (clockwise) to increase pressure.

Turn regulator screw OUT (counterclockwise) to decrease pressure. If an adjustment

is made, turn up the thermostat. Cycle the burner once or twice to properly seat the

adjustment spring in the valve. Re-check the pressure. When the outlet pressure is

right for the installation, remove the manometer and replace the cap. Check for a leak

at the pressure tap fitting.

WARNING

Valve outlet gas pressure must never exceed the value listed in

TABLE 11 (or as shown on the rating plate).

1) Gas Valve Pressure Tap Locations
The manifold includes a single-stage valve and a modulating valve (

FIGURE 11B).

Locate the outlet pressure tap just behind the orific adapter (See

FIGURE 11A above).

To check high fire outlet pressure, connect a manometer to the outlet pressure tap just

behind the orific adapter.
To check low-fire (bypass pressure), locate the 1/4” NPT pressure tap just behind the

orifice adapter as shown in

FIGURE 11C. Connect a manometer to the 1/4” pressure tap.

Low Fire

Outlet

Adjustment

Screw

High Fire Outlet

Adjustment Screw

Inlet

Pressure Tap

Two-Stage

Combination Valve

1/8” Outlet Pressure Tap

FIGURE 11A - Top Views of Valves Showing Outlet

Pressure Tap and Adjustment Locations

Single-Stage Combination Valves

CAUTION: DO NOT

bottom out the gas

valve regulator

adjusting screw.

This can result in

unregulated manifold

pressure causing

excess overfire and

heat exchanger

failure.

INSTRUCTIONS for single-

stage and two-stage gas

control options (Options

AG1, AG2, AG3, AG15,

AG16, AG60, AG61, AG62,

DG1, DG5, D12C)

The outlet pressure is regulated by the combination single or two stage gas valve. The

combination valve outlet pressure should be as shown in

TABLE 11, page 20, (for the

model size, gas type, gas control option, and altitude of the installation) or as noted on

the rating plate.

Modulating Valve in

Options AG8, AG9,

AG9H, AG40, DG2,

DG6, and D12B -- DO

NOT adjust.

To ensure an accurate high fire

reading at the single-stage valve, a

minimum signal of 20VDC must be

present at the modulating valve.

FIGURE 11B - Top View

of Modulating Valve in

AG8, AG9, AG9H, AG40,

DG2, DG6, and D12B

1/8” Outlet

Pressure

Tap

Inlet Pressure Tap

Adjust Outlet

Pressure

1/8” Outlet

Pressure Tap

Adjust Outlet

Pressure

Inlet

Pressure

Tap

INSTRUCTIONS

for ELECTRONIC

MODULATION Gas

Control Options AG8,

AG9, AG9H, AG40, DG2,

DG6, and D12B

Advertising