Reznor OH Unit Installation Manual User Manual

Page 19

Advertising
background image

Form I-OH, PN 120390 R5, Page 19

5) The pump will start and the burner ignite. With the burner ignited, check the oil

pressure and adjust, if necessary, to a pressure of 100 pounds for Sizes 95 and

140 or 150 pounds for Size 190.

Burner

Electrical

Switch

FIGURE 19 - Burner Pump

Check draft. Prior to continued operation, check to be sure that there is sufficient

draft for proper combustion. A draft of negative .01" w.c. is required over the fire.

When firing, the draft measurement in the stack should be a negative .03-.04" w.c.

Instructions for measuring draft:

1)

To measure draft over the fire, remove the metal plug in the observation door

(See

FIGURE 21, page 20.).

2) Insert air pressure gauge (such as Dwyer pressure gauge). Draft measurement

gauge must read a negative .01".

3) If measurement is not correct, adjust draft regulator until measurement is correct.
4) Replace plug.
5)

To measure flue draft, insert air pressure gauge in the 5/16" hole that was drilled

in the flue pipe halfway between the furnace and the draft regulator. Flue draft

measurement must be a negative .03-.04" w.c.

If there is insufficient draft, it will create a back pressure resulting in oil fumes

in the building and/or pulsating when the burner starts and stops. It may cause

excess deposits of soot. To correct this problem, the height of the chimney may

need to be increased and/or a UL listed draft inducer may need to be installed. If

a draft inducer is used, provision must be made to shut off the fuel supply to the

burner in the event of the failure of the draft inducer.

If there is too much draft, it could cause ignition problems, erratic burner, and

loss of thermal efficiency. To correct this problem, adjust the barometric damper

regulator to reduce the draft.

CAUTION: If there is a backdraft or downdraft, do not continue

operation of the heater until the situation is corrected. Equipment

and/or property damage could result. Back pressure (backdraft

or downdraft) may be caused by the chimney being lower than

surrounding objects, such as buildings, hills, trees, rooftops, etc.

It may be caused by an exhaust fan in the building. The air intake

in the room where the heater is installed must be sufficient size

so that there is no change in the draft reading in the flue with the

exhaust fan running.

Check combustion air shutter and air band settings. The heater is shipped

from the factory with the settings shown in the table in

FIGURE 21. Ordinarily,

Location of Primary

Ignition Control

(NOTE: Unit illustration

shows older model controller.)

FIGURE 20 - Heater Controls

Primary Ignition

Control with

Reset Button

Advertising