18
Model
number
Q6sP-
nominal
unit
Voltage
High
static
Kit #
single circuit (unit + Heater Kit) see note
Mca
MoP
9 kW
18 kW
30 kW
35 kW
9 kW
18 kW
30 kW
35 kW
Factory unit Electrical Data
-090Ca
208 - 230 V
Factory Std.
48 - 51
69.5 - 77 99.2 - 111 115 - 129
50 - 60
70 - 80
100 - 125 125 - 150
-090Da
460 V
27
39
54.8
64
30
40
60
70
-120Ca
208 - 230 V
Factory Std.
52 - 56
74 - 81
104 - 115 119 - 133
60 - 60
80 - 90
110 - 125 125 - 150
-120Da
460 V
29.1
42
58
67
30
45
60
70
Medium & High static Drive Electrical Data
-090Ca
208 - 230 V
921646
49 - 53
71 - 78
100 - 112 116 - 130
50 - 60
80 - 80
110 - 125 125 - 150
-090Da
460 V
27
39.2
56
64.4
30
40
60
70
-090Ca
208 - 230 V
921647
51 - 54
73 - 79.1
102 - 113 118 - 131
60 - 60
80 - 80
110 - 125 125 - 150
-090Da
460 V
29
40
56.2
66
30
40
60
70
-120Ca
208 - 230 V
921645
54 - 57
76 - 83
105 - 117 121 - 135
60 - 60
80 - 90
110 - 125 125 - 150
-120Da
460 V
29.9
43
59
68
30
45
60
70
notE: Nordyne specifically recommends the use of the 917468 Dual Circuit adapter kit for all applications of H5HK 30kW & 35kW Electric
Heat Kits.
table 3. Q6sP Electrical Data - single supply circuits