On the front side of the unit, Table 1 – Reznor R8HE Unit Installation Manual User Manual
Page 10

10
Figure 4. Refrigerant Service Ports & Air
Conditioning Condensate Drain Locations
HIGH SIDE
LOW SIDE
CONDENSATE
DRAIN
Securing
Screws
Figure 5. Internal Filter Rack Location
Table 1. External & Internal Filter Sizes
EXTERNAL FILTER SIZES
NOMINAL
COOLING
(TONNAGE)
FILTER SIZE
(IN. X IN.)
APPROXIMATE
AIR FLOW
RANGE (CFM)
APPROXIMATE
FILTER AREA
(SQ. IN.)*
2.0
20 x 25
600-900
450
2.5
20 x 30
750-1200
550
3.0
25 x 25
1100-1300
625
3.5
24 x 30
1200-1600
750
4.0
18 x 24 (2 required)
1400-1800
850
5.0
20 x 25 (2 required)
1700-2200
1000
INTERNAL FILTER SIZES
CABINET
HEIGHT
OUTDOOR
FAN
DIAMETER
FILTER SIZE
(IN. X IN.)
APPROXIMATE
AIR FLOW
RANGE (CFM)
APPROXIMATE
FILTER AREA
(SQ. IN.)*
30”
20
(2) 14”x25”
700 - 1300
700
24”
(1) 12”x20” and (1) 16”x25”
640
34”
20
(2) 16”x25”
900 - 1400
800
24”
(1) 12”x20” and (2) 10”x25”
740
38”
20”
(2) 18”x25”
1100 - 1600
900
24”
(1) 12”x20” and (2) 12”x25”
840
42”
20”
(2) 20”x25”
1300 - 1800
1000
24”
(1) 12”x20” and (2) 14”x25”
940
* Based on velocity of 300 ft/min for disposable filters.