Reznor R6GF Unit Installation Manual User Manual

Page 32

Advertising
background image

32

Status LED

Status LED Description

Status LED Troubleshooting Information

ALERT

Flash Code 3

(Yellow LED)

Short Cycling / Compressor
is running only briefly

•

Thermostat demand signal is intermittent

•

Low line voltage (contact utility if voltage at disconnect is low)

•

Excessive liquid refrigerant in compressor

•

Compressor bearings are seized

ALERT

Flash Code 4

(Yellow LED)

Locked Rotor

•

Run capacitor has failed

•

Low line voltage (contact utility if voltage at disconnect is low)

•

Check wiring connections

•

Excessive liquid refrigerant in compressor

•

Compressor bearings are seized

•

Measure compressor oil level

ALERT

Flash Code 5

(Yellow LED)

Open Circuit

•

Outdoor unit power disconnect is open

•

Compressor circuit breaker or fuse(s) is open

•

Compressor contactor has failed open

— Check compressor contactor wiring and connectors

— Check for compressor contactor failure (burned, pitted or open)
— Check wiring and connectors between supply and compressor
— Check for low pilot voltage at compressor contactor coil
— High pressure switch is open and requires manual reset

•

Open circuit in compressor supply wiring or connections

•

Unusually long compressor protector reset time due to extreme
ambient temperature

•

Compressor windings are damaged
— Check compressor motor winding resistance

ALERT

Flash Code 6

(Yellow LED)

Open Start Circuit
Current only in run circuit

•

Run capacitor has failed

•

Open circuit in compressor start wiring or connections
— Check wiring and connectors between supply and the

compressor S terminal

•

Compressor start winding is damaged
— Check compressor motor winding resistance

ALERT

Flash Code 7

(Yellow LED)

Open run circuit
Current only in start circuit

•

Open circuit in compressor run wiring or connections
— Check wiring and connectors between supply and the

compressor R terminal

•

Compressor run winding is damaged
— Check compressor motor winding resistance

ALERT

Flash Code 8

(Yellow LED)

Welded Contactor
Compressor always runs

•

Compressor contactor has failed closed

•

Thermostat demand signal not connected to module

ALERT

Flash Code 9

(Yellow LED)

Low Voltage
Control circuit < 17VAC

•

Control circuit transformer is overloaded

•

Low line voltage (contact utility if voltage at disconnect is low)

•

Check wiring connections

* Flash code number corresponds to a number of LED flashes, followed by a pause and then repeated. Trip and

alert LED’s flashing at same time means control circuit voltage is too low for operation.

Table 14. LED Diagnostics - Continued

Advertising