Installation instruction – Reznor R6GP Option - Installatin - Outside Air Damper - Light Commercial User Manual
Page 2

Fig ure 4
THUMB WHEEL
DAMPER ACTUATOR
INSTALLATION
INSTRUCTION
Outside Air Damper (Manual & Motorized)
Manual Damper 547864 used with R6GP & P6SP 072 & 090
Manual Damper 547874 used with Q6SP 090 & 120, P6SP & R6GP 120
Motorized Damper 547865 used with all P6SP, R6GP, Q6SP
V - OP ER A TION AND CHECK OUT
An spst low voltage controller is used to control the M8405
Actuator as follows:
A. Mid-position—when the controller circuit closes to provide
24 Vac to terminals T and X, the actuator is energized to
run to the adjustable mid-position (minimum position).
Adjustable minimum position can be reached from either the
fully closed or fully open position. From fully closed, the
actuator drives open to the minimum position; from fully open,
the actuator spring-returns to minimum position.
VI - SET TINGS AND AD JUST MENTS
The M8405 Damper Ac tu a tor has an in te gral thumbwheel for
outside air min i mum po si tion ad just ment. See Figure 4.
Outside Air Position Adjustment
1.
Connect the 24 Vac to the actuator at terminals T and X (D
is not connected).
2.
Adjust the thumbwheel on the actuator for desired outside
air minimum position.
SUPERSEDES 08-26-08
JUNE 16, 2011
NEI35OA07