Fig ure 4

THUMB WHEEL

DAMPER ACTUATOR

INSTALLATION

INSTRUCTION

Outside Air Damper (Manual & Motorized)

Manual Damper 547864 used with R6GP & P6SP 072 & 090

Manual Damper 547874 used with Q6SP 090 & 120, P6SP & R6GP 120

Motorized Damper 547865 used with all P6SP, R6GP, Q6SP

V - OP ER A TION AND CHECK OUT

An spst low voltage controller is used to control the M8405
Actuator as follows:

A. Mid-position—when the controller circuit closes to provide

24 Vac to terminals T and X, the actuator is energized to
run to the adjustable mid-position (minimum position).

Adjustable minimum position can be reached from either the
fully closed or fully open position. From fully closed, the
actuator drives open to the minimum position; from fully open,
the actuator spring-returns to minimum position.

VI - SET TINGS AND AD JUST MENTS

The M8405 Damper Ac tu a tor has an in te gral thumbwheel for
outside air min i mum po si tion ad just ment. See Figure 4.

Outside Air Position Adjustment

1.

Connect the 24 Vac to the actuator at terminals T and X (D
is not connected).

2.

Adjust the thumbwheel on the actuator for desired outside
air minimum position.

SUPERSEDES 08-26-08
JUNE 16, 2011

NEI35OA07