INSTALLATION INSTRUCTIONS FOR
559538 / 559539 / 559540 / 559541
ROOF CURBS USED WITH R6GN 150/180 UNITS
Note:
Condenser Pans can be lo cated on ei ther end de pend ing on in di vid ual ap pli ca tions.
INSTALLATION
INSTRUCTIONS
Fig ure 6
NORDYNE PART#
RSI PART#
A
559538
47-201-1108
8
559539
47-201-1114
14
559540
47-201-1118
18
559541
47-201-1124
24
*A
Step 5:
Install the condenser pan (C) as shown with opening over the desired duct location as shown in Figure 6.
Step 6:
Install both condenser pans (D) as shown in Figure 6.
Step 7:
If the curb is being assembled and moved to another location, attach the condenser pans as shown in "Details".
Step 8:
Place the ¾" x 1 ¼" Gasket on all of the top edges of the roof curb, including the condenser pans.
21
SUPPLY
RETURN
17 ½
15
3
16
77 ½
74
91
94 ½
1
¾
DUCT SIZES ARE:
Return 68 ½ x 17 ¼
Supply 73 ½ x 20 ½
ROOF OPENING:
74" Long
55" Wide
(D)
(C)
SHIFT RETURN DUCT TO
CLEAR FOR POWER ENTRY
(D)
37 ¼